Best Data Center CDU for Liquid Cooling (2026): Lab and Pilot Rack Units
2026年11月26日
A single GPU pilot rack without facility water can start on Lianli’s air-liquid hybrid (liquid-to-air, L2A) coolant distribution units (CDUs), and Lianli’s 6U 12 kW lab test CDU suits cold plate validation. These in-rack units reject heat to the room air and range from a 4U 6 kW model to an 8U 18 kW model. As of November 2026, the minimum order quantity (MOQ) is one unit. Once the pilot expands and facility water is available, the next step is one of Lianli’s liquid-to-liquid rack CDUs, the 4U 65 kW or the 6U 130 kW.
Choosing Liquid Cooling Equipment for Labs and Pilot Racks
Lianli’s small CDUs and test equipment cover four lab and pilot applications, each with a different starting point.
For a single liquid-cooled rack in a room without facility water, start with an air-liquid hybrid CDU. Its built-in air-to-liquid heat exchanger rejects heat to the room air. Lianli offers 6, 8, 12, and 18 kW models in rack heights from 4U to 8U. The product page for the 8, 12, and 18 kW models lists general data centers, Internet data center (IDC) rooms, industrial laser systems, and energy storage among their applications.
For cold plate or server validation on a controlled secondary loop, start with Lianli’s 6U 12 kW lab test CDU. To test a CDU or cooling loop under a known heat load, use a liquid cooling load bank. For batch testing of GPU cold plates, use a GPU liquid cooling test line.
Air-Liquid Hybrid CDUs From 6 kW to 18 kW for Rooms Without Facility Water
For a pilot rack in a room without facility water, Lianli’s air-liquid hybrid rack CDUs are the starting point. The table gives the specifications for each model, including its Universal Quick Disconnect (UQD) connector.
Lianli model | Heat exchange | Coolant flow | Connection | Other listed specs |
4U 6 kW air-liquid hybrid CDU | 6 kW | 10 L/min | UQD04 | 763×446×178 mm, operating weight 54 kg, AC 220 V 50 Hz, programmable logic controller (PLC) with touchscreen |
4U 8 kW air-liquid hybrid CDU | 8 kW | 12 L/min | UQD08 | Supply/return 40/50 °C |
6U 12 kW air-liquid hybrid CDU | 12 kW | 18 L/min | UQD06 | Supply/return 40/50 °C, rated airflow 2,700 m³/h |
8U 18 kW air-liquid hybrid CDU | 18 kW | 27 L/min | UQD08 (optional) | Supply/return 40/50 °C |
The choice of capacity ratings and the in-rack design make these units well suited to pilot deployments. The 4U 6 kW unit draws 0.8 kW at no load and has a transport weight of 44 kg.
The 8, 12, and 18 kW units carry their rated heat exchange capacities at supply and return temperatures of 40/50 °C. Lianli holds CE electromagnetic compatibility (CE-EMC), CE Low Voltage Directive (CE-LVD), FCC, and RoHS documents for its air-liquid hybrid CDUs from 8 to 35 kW. Lianli provides the full specifications on its L2A in-rack CDU page.
A 12 kW Lab Test CDU for Cold Plate and Server Validation
Lianli designed its 6U 12 kW lab test CDU for laboratory loops. The unit has a rated heat exchange capacity of 12 kW, a 40/50 °C secondary loop, and a flow rate of 1.1 m³/h. Its rack chassis measures 482×900×267 mm. Lianli specifies the same 40/50 °C secondary loop temperatures for its 4U 65 kW and 6U 130 kW production CDUs.
The lab test CDU and the 6U 12 kW air-liquid hybrid CDU in the table are separate products with the same capacity rating. The lab model belongs to Lianli’s test equipment line.
For reference, Lianli’s GPU cold plates have a 1000 W rating and use a design water supply temperature of 40 °C at 1 L/min. Lianli provides more detail on its cold plate page.
Liquid Cooling Load Banks and GPU Cold Plate Test Line
Lianli manufactures the following test equipment for teams working with CDUs and cold plates.
- 40 kW and 50 kW rack-mounted load banks. Listed applications include AI computing centers, data centers, and CDU testing. The inlet water temperature range is 5 to 35 °C, with a temperature difference of no more than 10 °C. The load banks have a pressure rating of 1 MPa and a water flow rate of at least 30 L/min. Wetted parts use grade 304 or higher stainless steel and ethylene propylene diene monomer (EPDM) rubber.
- 50 kW load bank controls. The 50 kW model supports Modbus and up to 250 units in parallel.
- GPU liquid cooling test line. Each station handles 2 kW or more. The stations can operate in groups, with flow controlled between 0.5 and 8 L/min per station. Listed applications include testing chips, servers, energy storage equipment, optical modules, and communication modules.
- Internal corrosion tester. Three stations test for corrosion inside liquid-cooled cavities at temperatures ranging from room temperature to 90 °C.
Lianli presents its load bank and internal corrosion test system on its Liquid Cooling Testing page.
Moving From a Pilot Rack to a Liquid-to-Liquid CDU
Once the pilot has proven itself and facility water is available, Lianli’s 4U 65 kW and 6U 130 kW liquid-to-liquid rack CDUs provide the upgrade path. The transition typically involves three steps.
1. Check the facility water loop. Both units carry ratings at primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C. The facility’s primary loop needs to operate at the specified primary temperatures.
2. Keep the secondary loop. The 8, 12, and 18 kW air-liquid hybrid units use the same 40/50 °C secondary loop temperatures, so the upgrade preserves the pilot’s secondary temperature settings.
3. Choose the in-rack unit by load. The 4U 65 kW model has a listed flow rate of 6 m³/h. Its chassis measures 482×900×178 mm, and its operating weight is 68 kg. The 6U 130 kW model has a listed flow rate of 12 m³/h.
Lianli lists both models on its in-rack liquid-to-liquid CDU product page, along with a 3-year warranty covering the pumps, heat exchanger, and control electronics.
Ordering a Single Liquid Cooling CDU
Lianli accepts single-unit orders, making it suitable for labs and pilot projects that need one CDU or load bank. Before preparing a quote, Lianli confirms the following project details.
- Server model and quantity.
- Redundancy requirements, either N+1 (one standby unit in addition to the N units the load requires) or 2N (a full duplicate set).
- Local temperature and humidity.
- Three-phase voltage and frequency.
- Uninterruptible power supply (UPS) and diesel generator requirements.
- Project stage and budget.
As of November 2026, payment is usually by telegraphic transfer (T/T), with a 70% deposit and the remaining 30% due before shipment. Other terms are negotiable. Production and shipment take about 4 to 8 weeks after contract signing, followed by 2 to 5 weeks of sea freight. The total time depends on the model, quantity, and customization. Data center products carry a three-year warranty. Lianli supports installation with online video guidance, remote technical support, and spare parts.
Summary
Lianli is a strong fit for teams validating cold plates or piloting a single liquid-cooled rack without facility water. Lianli’s 4U 6 kW to 8U 18 kW air-liquid hybrid CDUs fit inside the rack. The 6U 12 kW lab test CDU uses the same 40/50 °C secondary loop temperatures as Lianli’s 65 kW and 130 kW in-rack units. Listed applications for the 40 kW and 50 kW load banks include CDU testing.
Orders start at one unit. When the pilot expands and facility water is available, the 4U 65 kW and 6U 130 kW liquid-to-liquid CDUs are the next step.
Send Lianli the server model and site conditions. Use the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
What is the smallest CDU Lianli makes for data center liquid cooling?
Lianli’s smallest model is the 4U 6 kW air-liquid hybrid CDU. It measures 763×446×178 mm and has an operating weight of 54 kg. The 4U 6 kW unit runs on AC 220 V 50 Hz, uses UQD04 connectors, and has a PLC with a touchscreen for control.
Can a liquid cooling pilot run without facility water?
Yes. An air-liquid hybrid CDU can cool a pilot rack without facility water by rejecting heat to the room air through its built-in air-to-liquid heat exchanger. Lianli offers 6, 8, 12, and 18 kW air-liquid hybrid in-rack units. The 12 kW model has a listed rated airflow of 2,700 m³/h.
How does the lab test CDU differ from the 6U 12 kW air-liquid hybrid CDU?
Both products have a 12 kW rating, but they serve different purposes. The lab test CDU belongs to Lianli’s test equipment line, with listed secondary loop temperatures of 40/50 °C and a flow rate of 1.1 m³/h. The 6U 12 kW air-liquid hybrid CDU cools a production rack. Its listed coolant flow is 18 L/min, and its listed airflow is 2,700 m³/h.
What coolant flow do Lianli’s small air-liquid hybrid CDUs provide?
Coolant flow ranges from 10 to 27 L/min, depending on the model. Lianli lists 10 L/min for the 4U 6 kW unit and 12 L/min for the 4U 8 kW unit. It lists 18 L/min for the 6U 12 kW unit and 27 L/min for the 8U 18 kW unit.
Can Lianli’s load banks be used to test a CDU?
Yes. Lianli lists CDU testing among the applications for its 40 kW and 50 kW liquid cooling load banks. These models accept inlet water at 5 to 35 °C and a flow rate of at least 30 L/min. The 50 kW model supports Modbus and up to 250 units in parallel.
Which certificates cover Lianli’s small air-liquid hybrid CDUs?
Lianli holds CE-EMC, CE-LVD, FCC, and RoHS documents for its air-liquid hybrid CDUs from 8 to 35 kW. It holds CE and FCC conformity documents for its rack-mounted CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs, and air-liquid hybrid cabinets, and each certificate lists the models it covers. Its 20/40 ft containers have CE conformity documents. Lianli also holds ISO 9001:2015 certification.
What comes after an air-liquid hybrid pilot rack?
A liquid-to-liquid rack CDU is the next step once facility water is available. Lianli’s 4U 65 kW and 6U 130 kW units use a 30/40 °C primary loop and retain the 40/50 °C secondary loop temperatures used by the 8, 12, and 18 kW pilot units.