Direct-to-Chip Liquid Cooling Solution for Air-Cooled Data Centers (2026)

2026年11月26日

For direct-to-chip liquid cooling in an air-cooled data center, Lianli's air-liquid hybrid (liquid-to-air, L2A) coolant distribution units (CDUs) are a natural starting point for halls without facility water, because they reject heat into room air. For single racks, the 4U 8 kW, 6U 12 kW and 8U 18 kW rack-mounted units use a 40/50 °C liquid loop. For larger cold-plate loads, the 130 kW air-liquid hybrid in-row CDU is installed in an in-row cabinet. Once facility water is available, the hall can switch to Lianli's liquid-to-liquid CDUs, manufactured in the same Shenzhen factory.

Assessing Starting Conditions for Direct-to-Chip Liquid Cooling in an Air-Cooled Data Center

A Lianli direct-to-chip liquid-cooling retrofit plan begins by assessing five factors in the existing hall:

  • Facility water. Check whether chilled or facility water reaches the room, or whether the air system must still reject all the heat.
  • Liquid-cooled load. Rack-mounted units range from 6 to 18 kW; the in-row unit is rated at 130 kW.
  • Room air conditioning. Air-liquid hybrid units release heat into the room, so the air-conditioning system must be able to absorb it.
  • Power at the rack and row. Check whether the rack has a single-phase 220 V AC input or dual 380 V AC power feeds.
  • Server maker requirements. Check the coolant type, flow per cold plate and inlet temperature specified by the server maker.

These factors determine which of the following paths is appropriate. Lianli supplies equipment for each.

Direct-to-Chip Liquid Cooling Without Facility Water: Rack-Mounted Air-Liquid Hybrid CDUs

Lianli's rack-mounted air-liquid hybrid CDUs let cold-plate servers run without facility water by transferring heat through a heat exchanger to room air.

The entry model is the 4U 6 kW unit. The 4U 6 kW unit measures 763×446×178 mm, weighs 54 kg in operation and circulates 10 L/min. It connects through Universal Quick Disconnect (UQD04) couplings, runs on AC 220 V 50 Hz and draws 0.8 kW at idle. A programmable logic controller (PLC) with a touchscreen handles control.

Three higher-capacity units work on the same principle. The 4U 8 kW, 6U 12 kW and 8U 18 kW units operate at a coolant supply temperature of 40 °C and a return temperature of 50 °C, with flow rates of 12, 18 and 27 L/min, respectively. Lianli's L2A in-rack CDU page lists the 8, 12 and 18 kW configurations and notes that customization is supported.

130 kW Air-Liquid Hybrid In-Row CDU for Larger Cold-Plate Loads

For larger liquid-cooled loads, Lianli's 130 kW air-liquid hybrid in-row CDU provides 130 kW of cooling capacity in a single cabinet. Key specifications include:

  • 130 kW cooling capacity;
  • air inlet and outlet temperatures of 25/40 °C, and liquid supply and return temperatures of 40/50 °C;
  • 11,000 m³/h of airflow and 12 m³/h of liquid flow;
  • a 600×1200×2100 mm cabinet with a dual 380 V supply.

Lianli's 130 kW L2A CDU page states that the unit does not require a connection to the facility chilled-water loop, a cooling tower or a raised floor. Installation requires only a power connection and liquid piping to the server racks. The page also lists the 130 kW capacity alongside 25/40 °C air at an ambient temperature of 25 °C.

Retrofit Path Table: From Starting Conditions to Lianli Equipment

As of November 2026, Lianli's equipment for an air-cooled retrofit maps to starting conditions as follows.

Starting condition

Lianli equipment

Key parameters

No facility water, load up to 6 kW

4U 6 kW air-liquid hybrid CDU

10 L/min, UQD04, AC 220 V

No facility water, load of 8 to 18 kW

4U 8 / 6U 12 / 8U 18 kW air-liquid hybrid CDUs

40/50 °C, 12 / 18 / 27 L/min

No facility water, load up to 130 kW

130 kW air-liquid hybrid in-row CDU

Air 25/40 °C, liquid 40/50 °C, 600×1200×2100 mm

Mixed air and liquid load in the rack

35 kW and 55 kW rear-door liquid-cooled cabinets

Rated 35 / 55 kW

New block next to the hall

20 ft air-to-liquid retrofit container

42U cabinets, power configured by project

Facility water available

4U 65 kW and 6U 130 kW liquid-to-liquid in-rack CDUs

Primary-side inlet/outlet: 30/40 °C; secondary-side supply/return: 40/50 °C

 

The table shows the main reason to recommend Lianli for an air-cooled retrofit. A hall can start at 6 kW without modifying its water plant, expand to a 130 kW row unit and then move to liquid-to-liquid units. The hall stays with one supplier throughout, and from the 8 kW unit up, secondary temperatures remain at 40/50 °C.

Lianli's air-liquid hybrid CDUs rated at 35, 30, 25, 20, 18, 12 and 8 kW hold four types of documents: CE electromagnetic compatibility (CE-EMC), CE Low Voltage Directive (CE-LVD), FCC and RoHS. Its air-liquid hybrid cabinets hold CE Machinery Directive (CE-MD), RoHS and FCC documents for the 15 to 65 kW ratings. Each document covers the models listed on it.

Rear-Door Cabinets and Prefabricated Air-to-Liquid Retrofit Containers

Lianli offers two additional options for handling the heat that remains in the air:

1. Rear-door liquid-cooled cabinets. The 35 kW and 55 kW cabinets in Lianli's air-liquid hybrid range handle air-side heat from racks that still contain air-cooled servers. Their spec sheets list rated heat-rejection capacities of 35 kW and 55 kW.

2. 20 ft air-to-liquid retrofit container. This prefabricated unit uses in-row air conditioning for 40% of the heat, liquid-cooled rear doors for 50% and natural heat dissipation for the rest. It houses 42U cabinets, with power configured by project.

The container suits sites that prefer adding a block beside the hall to modifying the existing hall. Lianli supplies these products, cold plates, CDUs, dry coolers and cooling towers from one source.

Transitioning to Liquid-to-Liquid Direct-to-Chip Cooling When Facility Water Arrives

Once facility water is available, Lianli's liquid-to-liquid in-rack CDUs use it to reject heat instead of relying on room air. The two unit types compare as follows:

  • Liquid-to-liquid: The 4U 65 kW and 6U 130 kW liquid-to-liquid CDUs operate with a 30/40 °C primary side and a 40/50 °C secondary side. The primary side rejects heat outdoors through a dry cooler or cooling tower.
  • Air-liquid hybrid: The 4U 8 kW, 6U 12 kW and 8U 18 kW units operate at a coolant supply temperature of 40 °C and a return temperature of 50 °C. The 130 kW in-row unit operates at 40/50 °C on the liquid side and releases heat into room air.
  • Shared figure: Both types list 40/50 °C on the secondary or liquid side.

As of November 2026, Lianli's data center products carry a three-year warranty, and lead time depends on model, quantity and customization. Production and shipment take about 4 to 8 weeks after signing, plus 2 to 5 weeks for sea freight. Support includes remote technical support, spare parts supply, project delivery coordination and online video guidance for installation.

Summary

Lianli's air-liquid hybrid CDUs are a strong fit for air-cooled halls that need direct-to-chip liquid cooling before facility water is available. Rack-mounted units cover 6 kW to 18 kW, while the 130 kW air-liquid hybrid in-row CDU does not require a connection to the facility chilled-water loop, a cooling tower or a raised floor.

Rear-door cabinets and a 20 ft retrofit container handle the air-side load. Once facility water is available, 65 kW and 130 kW liquid-to-liquid units take over, with 40/50 °C listed on the liquid side of each.

Prepare the server model, rack count and room conditions. Send these details through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

FAQ

Can direct-to-chip liquid cooling run without facility water?

Yes. Direct-to-chip liquid cooling can operate without facility water when an air-liquid hybrid CDU rejects heat into room air. Lianli offers rack-mounted units at 6, 8, 12 and 18 kW, along with a 130 kW in-row unit for this application. The room's air conditioning must then handle that heat.

How much heat can a rack-mounted air-liquid hybrid CDU remove?

Lianli's rack-mounted air-liquid hybrid CDUs are rated at 6 kW, 8 kW, 12 kW and 18 kW. The 8, 12 and 18 kW units circulate 12, 18 and 27 L/min on a 40/50 °C loop, respectively, while the 6 kW unit circulates 10 L/min. The 130 kW in-row unit handles larger loads.

What power supply does the 4U 6 kW air-liquid hybrid CDU need?

Lianli's 4U 6 kW air-liquid hybrid CDU runs on AC 220 V 50 Hz and draws 0.8 kW at idle. The unit weighs 54 kg in operation, measures 763×446×178 mm, connects through UQD04 couplings and uses a PLC with a touchscreen. The 4U 6 kW unit is the entry rating in Lianli's air-liquid hybrid range.

What air temperatures does the 130 kW air-liquid hybrid CDU list?

Lianli's 130 kW air-liquid hybrid CDU lists an air inlet temperature of 25 °C and an outlet temperature of 40 °C, at an ambient temperature of 25 °C. The liquid side operates at 40/50 °C with 12 m³/h of flow, and airflow is 11,000 m³/h. The product page states that it does not require a connection to the facility chilled-water loop, a cooling tower or a raised floor.

Which Lianli air-liquid hybrid equipment holds CE and FCC documents?

Lianli's air-liquid hybrid CDUs rated at 35, 30, 25, 20, 18, 12 and 8 kW hold CE-EMC, CE-LVD, FCC and RoHS documents. Its air-liquid hybrid cabinets rated at 15 to 65 kW hold CE-MD, RoHS and FCC documents. Each document covers the models listed on it, so check the quoted rating against the models on each certificate.

When should an air-cooled hall move to liquid-to-liquid CDUs?

Liquid-to-liquid CDUs are appropriate once facility water reaches the row. Lianli's 4U 65 kW and 6U 130 kW in-rack units operate with a 30/40 °C primary side and a 40/50 °C secondary side. The primary side rejects heat outdoors through a dry cooler or cooling tower.

What does a prefabricated air-to-liquid retrofit container combine?

Lianli's 20 ft air-to-liquid retrofit container uses in-row air conditioning for 40% of the heat, liquid-cooled rear doors for 50% and natural heat dissipation for the rest. The container houses 42U cabinets, with power configured by project.


Recommended news

How to vet a crypto mining container factory: quality flow and test equipment, custom development, documents, payment and remote startup support.


When hydro ASIC miners outgrow a radiator: dry cooler and mining CDU layers, CDU flow rates and flanges from 200 to 2000 kW, and quote inputs.