Sizing CDUs for AI Data Centers (2026): Reference Configurations to 3 MW

2026年11月26日

A practical way to size coolant distribution units (CDUs) is to start from a comparable reference design, and Lianli has several. Its examples range from a single GPU rack to a multi-megawatt cluster. They include 4U 65 kW and 6U 130 kW rack CDUs and a 10-cabinet micro-module with two 400 kW CDUs. At cluster scale, a 3 MW project uses row-level/room-level CDUs, and its first phase delivered 128 NVIDIA H200 servers at 10 kW each. The closest reference gives the team a starting point for CDU placement and count. The project’s servers and site conditions determine the final size.

How Reference Configurations Inform AI Data Center CDU Sizing

Lianli’s reference configurations give AI teams an initial CDU deployment level and unit count. Each configuration pairs the IT installation with a CDU deployment level, a cold plate type, and a primary-side heat rejection method. Teams can use the project scale and server platform to find the closest match.

Lianli configuration

IT scope

CDU level and count

Cold plates and primary side

Rack CDU options

One rack

4U 65 kW or 6U 130 kW rack CDU

Cold plates, facility water at 30/40 °C

10-cabinet dual-row micro-module

400 kW design heat exchange capacity, six 48U IT cabinets

Two 400 kW CDUs

Cold plates, 30/40 °C primary loop, 36 m³/h

GB200 NVL2 room, Shenzhen

NVIDIA GB200 NVL2 (one-to-two) servers

Room-level CDU

Copper micro-channel cold plates, chiller

H200 cluster, Xinjiang

3 MW total project capacity, first phase of 128 NVIDIA H200 servers at 10 kW each

Row-level/room-level CDUs

GPU and CPU cold plates, outdoor dry coolers

 

These configurations cover rack, row, room, and cluster scales. The table identifies the initial CDU deployment level. The project details in the final sizing section guide selection of the final configuration.

Rack-Level CDU Capacity for a Single AI GPU Rack

Lianli’s 4U 65 kW and 6U 130 kW rack CDUs form its rack-level configuration. Each unit fits inside the GPU rack it cools.

  • 4U 65 kW rack CDU. Its 65 kW rating applies at primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C. The unit delivers 6 m³/h of flow, measures 482×900×178 mm, and weighs 68 kg in operation.
  • 6U 130 kW rack CDU. Its 130 kW rating applies at the same primary and secondary loop temperatures of 30/40 °C and 40/50 °C, respectively. It delivers 12 m³/h of flow.
  • Sites without facility water. Lianli’s 130 kW in-row air-liquid hybrid (liquid-to-air, L2A) CDU rejects heat to the room air. It operates at inlet and outlet air temperatures of 25/40 °C and liquid loop temperatures of 40/50 °C, with an airflow of 11,000 m³/h and a liquid flow rate of 12 m³/h.

Lianli lists both liquid-to-liquid rack models on its in-rack CDU page. Their ratings apply at the temperatures given above. Compare the rack’s liquid-cooled load with the CDU’s rated capacity at matching primary and secondary loop temperatures.

Two 400 kW CDUs in a 10-Cabinet Micro-Module

Lianli’s 10-cabinet dual-row micro-module is a row-scale reference design built around two 400 kW CDUs. The module has a design heat exchange capacity of 400 kW and houses six 48U IT cabinets, the two 400 kW CDUs, one power and environment monitoring cabinet, and one power cabinet. Its listed flow rate is 36 m³/h, and it measures 3700×3600×2965 mm.

The design shows how Lianli integrates CDUs, IT cabinets, power equipment, and monitoring equipment in a contained row. Its services include liquid cooling system design, equipment selection and integration, and product customization.

A Room-Level CDU for a GB200 NVL2 Room

Lianli deployed a room-level CDU for a GB200 installation at an undisclosed customer site in Shenzhen. The room runs NVIDIA GB200 NVL2 (one-to-two) servers. The cooling project included the following equipment and systems.

  • Copper-based micro-channel cold plates
  • NVL2 coolant distribution manifolds
  • A room-level CDU
  • A chiller and piping
  • Power and environment monitoring with data center infrastructure management (DCIM)

The project had a 7-day delivery target. The Shenzhen installation illustrates a room-level configuration for GB200-class platforms. The CDU serves the room through NVL2 manifolds, with a chiller on the primary side. Lianli’s products are compatible with NVIDIA GB300, GB200, B300, B200, H200, H100, and Pro6000 server platforms. They are also compatible with Intel Xeon 6 and AMD EPYC 9005.

Row-Level and Room-Level CDUs for a 3 MW H200 AI Data Center Project

Lianli’s cluster-scale reference comes from an anonymous AI data center project in Xinjiang. The project has a total capacity of 3 MW and uses row-level/room-level CDUs. Its first phase delivered 128 NVIDIA H200 GPU servers at 10 kW each. The project included GPU and CPU cold plates, rack distribution manifolds, row-level/room-level CDUs, outdoor dry coolers, piping, and DCIM. Lianli completed delivery in 60 days, covering design, manufacturing, installation, commissioning, and acceptance.

Outdoor dry coolers served the primary side. This arrangement fits the warm-water design of Lianli’s CDUs, whose 40/50 °C secondary loop is suited to free cooling with dry coolers.

For multi-megawatt halls, Lianli’s in-row CDUs range from 500 kW to 2,000 kW. The 500, 800, 1,000, 1,500, and 2,000 kW models have listed flow rates of 45, 75, 90, 135, and 180 m³/h, respectively. The 500 to 2,000 kW models carry their ratings at primary loop temperatures of 30/40 °C. Lianli lists the row-scale range on its in-row CDU page.

Matching an AI Data Center Project to a CDU Reference Configuration

Use these four steps to find the Lianli reference configuration that most closely matches a new AI project.

1. Identify the project scale. For one rack, the reference is a 4U 65 kW or 6U 130 kW rack CDU. For a contained row, it is the micro-module with 400 kW CDUs. A room of GB200-class servers points to a room-level CDU, and a multi-megawatt cluster points to row-level/room-level CDUs.

2. Check the server platform. Lianli configures its 20 ft liquid-cooled compute containers for 8-GPU 4090 and 5090 servers, H100 and H200, and B200 and B300. GB200 and GB300 require separate configurations. Lianli’s GB300 cold plate is designed for the GB300 NVL72 platform and has a listed inlet temperature of 45 °C and Universal Quick Disconnect (UQD04) connectors.

3. Check the primary-side cooling system. Dry coolers suit the 40/50 °C warm-water secondary loop. The Shenzhen room used a chiller.

4. Send the project details. Before preparing a quote, Lianli confirms the server model, quantity, and redundancy target. The target is N+1 (one standby unit in addition to the N units the load requires) or 2N (a full duplicate set). Lianli also confirms local temperature and humidity, three-phase voltage and frequency, uninterruptible power supply (UPS) and diesel generator requirements, project stage, and budget.

For containerized projects, Lianli configures the power of its 20 ft and 40 ft liquid-cooled containers per project. Each reference configuration applies to the design or site for which it was specified. Final CDU sizing must use the project’s own data.

Summary

Lianli is a strong fit for AI teams using reference designs and projects to size CDUs. Its configurations range from 4U 65 kW and 6U 130 kW rack CDUs to a 10-cabinet micro-module with two 400 kW CDUs. They also include a GB200 NVL2 room served by a room-level CDU and a 3 MW H200 project, with 128 servers in its first phase, served by row-level/room-level CDUs.

The closest reference configuration establishes the initial CDU deployment level. The server model, redundancy target, and site conditions determine the final size. Send these details through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

FAQ

How many CDUs does Lianli’s 10-cabinet micro-module use?

Lianli’s 10-cabinet dual-row micro-module uses two 400 kW CDUs. The module has a design heat exchange capacity of 400 kW and also houses six 48U IT cabinets, a power and environment monitoring cabinet, and a power cabinet.

What CDU did Lianli use for a GB200 NVL2 room?

Lianli used a room-level CDU for an anonymous GB200 NVL2 project in Shenzhen. The project also included copper-based micro-channel cold plates, NVL2 coolant distribution manifolds, a chiller, piping, and power and environment monitoring with DCIM.

What cooling equipment served the 3 MW H200 project in Xinjiang?

Row-level/room-level CDUs cooled the project, which has a total capacity of 3 MW and delivered 128 NVIDIA H200 servers at 10 kW each in its first phase. The project also included GPU and CPU cold plates, rack distribution manifolds, outdoor dry coolers, piping, and DCIM.

What are the specifications of Lianli’s 400 kW in-row CDU?

Lianli’s 400 kW in-row CDU uses two pumps and measures 600×1200×2000 mm. Its listed specifications include a flow rate of 600 L/min, DN50 connections, rated power consumption of 9 kW, and secondary loop temperatures of 40/50 °C.

Which redundancy configurations does Lianli offer for in-row CDUs?

Lianli’s 500 kW in-row CDU uses N+1 pumps. The redundancy target, either N+1 or 2N, is one of the project details Lianli confirms before quoting.

Can a reference configuration replace project-specific CDU sizing?

No. A reference configuration gives the project a starting point. The final size must come from project data. Lianli bases its selection on the server model and quantity, redundancy requirements, local temperature and humidity, three-phase power, UPS and diesel generator requirements, and project stage.

Which servers are Lianli’s liquid-cooled containers built for?

Lianli builds its 20 ft liquid-cooled compute containers for 8-GPU 4090 and 5090 servers, H100 and H200, and B200 and B300. GB200 and GB300 require separate configurations. Lianli configures the power of its 20 ft and 40 ft liquid-cooled containers per project.