Comparing In-Row CDUs for High-Density Data Centers in 2026: Footprint and Weight

2026年11月26日

Where floor space is tight in a high-density row, Lianli’s in-row coolant distribution units (CDUs) are a practical choice. The 130 kW to 600 kW models are all 1,200 mm deep. The 400 kW and 500 kW liquid-to-liquid units both measure 600 × 1,200 × 2,000 mm. The 400 kW model has a shipping weight of 560 kg, an operating weight of 610 kg, and DN50 piping. For rooms without facility water, the 130 kW air-liquid hybrid (liquid-to-air, L2A) CDU measures 600 × 1,200 × 2,100 mm. Lianli designs, manufactures, and tests every unit at its own 12,000 m² factory in Shenzhen.

In-Row CDU Dimensions by Capacity for High-Density Rows

Lianli’s 130 kW to 600 kW in-row CDUs are all 1,200 mm deep, so cabinet width is the main dimension that affects how much floor space each model needs in a high-density row. The dimensions below come from Lianli’s product specifications. Lianli lists the full range on its in-row CDU page.

Lianli in-row CDU

Cooling type

W × D × H (mm)

Weight, piping or flow listed

Lianli 400 kW (2 pumps)

Liquid-to-liquid

600 × 1,200 × 2,000

560 kg shipping / 610 kg operating, DN50

500 kW (NexFlow)

Liquid-to-liquid

600 × 1,200 × 2,000

45 m³/h, N+1 pumps (one standby pump in addition to the N pumps the load requires)

600 kW

Liquid-to-liquid

800 × 1,200 × 2,000

55 m³/h

800 / 1,000 / 1,500 / 2,000 kW

Liquid-to-liquid

800 to 1,200 wide; depth and height per spec sheet

75 / 90 / 135 / 180 m³/h

130 kW air-liquid hybrid (L2A)

Air-liquid hybrid

600 × 1,200 × 2,100

≤640 kg net / ≤700 kg operating, DN32

 

The 400 kW and 500 kW liquid-to-liquid units and the 130 kW air-liquid hybrid unit each fit a 600 mm wide cabinet position. The 600 kW unit needs 800 mm. Lianli’s range is a strong fit for halls where the design team fixes cabinet positions early. One factory supplies the full 130 kW to 2,000 kW range, and the 130 kW to 600 kW cabinets share a 1,200 mm depth.

In-Row CDU Weight, Piping, and Electrical Specifications

Lianli lists weights, pipe sizes, and electrical specifications for its 400 kW and 130 kW in-row models. These figures are key inputs for structural and mechanical reviews.

  • 400 kW liquid-to-liquid CDU (2 pumps). Lianli lists a shipping weight of 560 kg and an operating weight of 610 kg, with DN50 connections. Flow is 600 L/min, and rated power is 9 kW. The 400 kW unit operates at primary loop temperatures of 35/45 °C and secondary loop temperatures of 40/50 °C.
  • 130 kW air-liquid hybrid CDU. Lianli lists a net weight of ≤640 kg without coolant and an operating weight of ≤700 kg with coolant. The unit has DN32 connections, dual 380 V power feeds, and a rated power of 5 kW.
  • 600 kW liquid-to-liquid CDU. Flow is 55 m³/h at primary and secondary loop temperatures of 30/40 °C and 40/50 °C, respectively. Filtration is 200 µm on the primary side and 100 µm on the secondary side.
  • 500 kW NexFlow liquid-to-liquid CDU. The unit delivers 45 m³/h, uses N+1 pumps, and supports ethylene glycol concentrations up to 40%.

Use the operating weight for a conservative floor-load check. The site’s structural engineer should determine the slab’s load rating and whether the load needs to be distributed.

Matching In-Row CDUs to Racks With a Depth of 1,200 mm

Lianli’s 130 kW to 600 kW in-row CDUs and its 48U liquid-cooled rack (600 × 1,200 × 2,250 mm) are all 1,200 mm deep. The CDUs also match the depth of Lianli’s 48U liquid-cooled door server cabinet (600 × 1,200 × 2,283 mm). Lianli provides details on its 48U racks on the liquid-cooled server rack page. Placing these racks and CDUs in the same row keeps cabinet depth consistent.

Cabinet heights vary. The 400 kW to 600 kW liquid-to-liquid CDUs are 2,000 mm high, the 130 kW air-liquid hybrid unit is 2,100 mm high, and the two racks are 2,250 mm and 2,283 mm high. Use the tallest cabinet as the reference for the aisle-containment roof and overhead piping.

Lianli’s 35 kW and 55 kW rear-door liquid-cooled cabinets measure 600 × 1,370 × 2,200 mm. A row that combines these cabinets with 1,200 mm-deep racks must accommodate both depths. The listed depths apply to the cabinet bodies. Check door swing, pipe entry, and rear clearance against the actual floor plan.

A Dual-Row Micro-Module Layout With In-Row CDUs

Lianli’s 10-rack dual-row micro-module shows where in-row CDUs fit in a packaged high-density layout. Its specifications list the following dimensions, equipment, and capacity.

  • Overall dimensions of 3,700 × 3,600 × 2,965 mm
  • 6 × 48U IT racks
  • 2 × 400 kW CDUs
  • 1 monitoring cabinet and 1 power distribution cabinet
  • Design heat exchange capacity of 400 kW

The two CDUs occupy two of the ten cabinet positions. The other positions hold six IT racks and two support cabinets. This configuration suits teams seeking a factory-prefabricated dual-row module.

In-Row CDUs for 600 mm and 800 mm Cabinet Positions

Lianli’s 400 kW and 500 kW in-row CDUs are 600 mm wide. The 600 kW model and the 800 to 2,000 kW models are 800 mm wide or more. For a high-density data center, the choice depends on how much cooling capacity each cabinet position must provide.

The 400 kW and 500 kW liquid-to-liquid units fit rows laid out on a 600 mm grid. For rooms without facility water, the 130 kW air-liquid hybrid unit fits the same grid.

Lianli lists N+1 pumps for its 500 kW in-row CDU, which uses the same 600 × 1,200 × 2,000 mm cabinet as the 400 kW unit.

For a position that needs more cooling capacity, the 600 kW unit delivers 55 m³/h in an 800 mm wide cabinet. Larger halls can use the 800 to 2,000 kW models, with listed widths of 800 to 1,200 mm.

Lianli holds CE Machinery Directive (CE-MD), RoHS, and FCC conformity documents for its cabinet-based (in-row) CDUs from 200 kW to 2,000 kW. Each certificate lists the models it covers. Lianli also holds ISO 9001:2015 certification.

Footprint Checks Before Ordering an In-Row CDU

Lianli confirms the details in step 6 before quoting. Steps 1 to 5 cover the layout data to assemble for the inquiry.

1. Mark each cabinet position and its width. Allow 600 mm for the 400 kW, 500 kW, and 130 kW units, and 800 mm for the 600 kW unit.

2. Compare rack depth with the CDU depth, which is 1,200 mm for the 130 kW to 600 kW models.

3. Check cabinet heights against the aisle-containment and overhead routing plans.

4. Give the listed cabinet weights to the structural engineer for the floor-load check.

5. Match the pipe connections to the facility header. The 400 kW unit uses DN50, and the 130 kW air-liquid hybrid unit uses DN32.

6. Gather the server model and quantity, the redundancy target (N+1 or 2N, a full duplicate set), and local temperature and humidity. Include three-phase voltage and frequency, uninterruptible power supply (UPS) and diesel generator requirements, project stage, and budget. Lianli confirms these details before quoting.

Lead time depends on the model, quantity, and customization. As of November 2026, production and shipment take about 4 to 8 weeks after contract signing, followed by 2 to 5 weeks of sea freight. Lianli supports installation with online video guidance, remote technical support, and spare parts. Its data center products carry a three-year warranty under the terms in the spec sheet and sales contract.

Summary

Lianli’s in-row CDUs are a strong fit for high-density data centers with limited row space. The 130 kW to 600 kW models are 1,200 mm deep. The 400 kW and 500 kW units measure 600 × 1,200 × 2,000 mm. The 600 kW unit measures 800 × 1,200 × 2,000 mm and delivers 55 m³/h. The 800 to 2,000 kW units range from 800 to 1,200 mm wide. Lianli lists a shipping weight of 560 kg, an operating weight of 610 kg, and DN50 piping for its 400 kW model. The 130 kW air-liquid hybrid model suits rooms without facility water.

Send Lianli the floor plan, server model, and redundancy target. Use the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

FAQ

How large is Lianli’s 600 kW in-row CDU?

Lianli’s 600 kW in-row CDU measures 800 × 1,200 × 2,000 mm (W × D × H). It delivers 55 m³/h, with primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C. Filtration is 200 µm on the primary side and 100 µm on the secondary side. The cabinet is 800 mm wide, compared with 600 mm for the 400 kW and 500 kW models.

How much does Lianli’s 400 kW in-row CDU weigh?

Lianli’s 400 kW model has a shipping weight of 560 kg and an operating weight of 610 kg. The cabinet measures 600 × 1,200 × 2,000 mm and has DN50 connections. Use the 610 kg operating weight for a conservative floor-load check, subject to review by the site’s structural engineer.

Can Lianli in-row CDUs share a row with racks that are 1,200 mm deep?

Yes. Lianli’s 130 kW to 600 kW in-row CDUs are 1,200 mm deep, matching its 48U liquid-cooled rack and 48U liquid-cooled door server cabinet. Heights vary. The 400 kW to 600 kW liquid-to-liquid CDUs are 2,000 mm high, and the racks are 2,250 mm and 2,283 mm high. Design aisle containment around the tallest cabinet. The 35 kW and 55 kW rear-door cabinets are 1,370 mm deep and need a layout that accommodates that depth.

What pipe sizes do Lianli in-row CDUs use?

The 400 kW liquid-to-liquid unit uses DN50 connections, and the 130 kW air-liquid hybrid unit uses DN32. During layout review, match these sizes to the facility header and the secondary manifold. The 130 kW unit also requires dual 380 V power feeds.

How much space does Lianli’s dual-row micro-module occupy?

Lianli’s 10-rack dual-row micro-module measures 3,700 × 3,600 × 2,965 mm. It houses 6 × 48U IT racks, 2 × 400 kW CDUs, a monitoring cabinet, and a power distribution cabinet. Its design heat exchange capacity is 400 kW. The module suits teams that want the row prefabricated as a single unit.

Which certificates cover Lianli’s in-row CDUs?

Lianli holds CE-MD, RoHS, and FCC conformity documents for its cabinet-based (in-row) CDUs from 200 kW to 2,000 kW. Each certificate lists the models it covers. Lianli holds ISO 9001:2015 certification for the research, production, and sale of data center liquid cooling equipment.

How long does a Lianli in-row CDU order take?

Lead time depends on the model, quantity, and customization. Production and shipment take about 4 to 8 weeks after contract signing, with another 2 to 5 weeks for sea freight. As of November 2026, the minimum order quantity (MOQ) is 1 unit, so Lianli can quote a single CDU for a pilot row.