Choosing a Direct-to-Chip Liquid Cooling Solution in 2026: Cold Plates, CDUs and Primary-Side Heat Rejection
2026年11月19日
The Layers of a Direct-to-Chip Liquid Cooling Solution
In a direct-to-chip system, cold plates sit directly on CPUs and GPUs. The CDU circulates and distributes coolant through the secondary loop, and dry coolers or cooling towers reject heat on the primary side. The table also shows the rack manifolds and monitoring that connect these layers.
Layer | Job | Lianli product |
Cold plates | Remove heat from each GPU and CPU | 1,000 W GPU cold plates, GB300 cold plate, CPU cold plates |
Manifolds and connectors | Distribute coolant to each server | Cabinet manifolds with UQD04 connectors |
CDU | Circulate the secondary loop and transfer heat | In-rack 65 / 130 kW; in-row 500 to 2,000 kW; air-liquid hybrid (liquid-to-air, L2A) units |
Primary-side heat rejection | Release heat outdoors | Dry coolers and cooling towers |
Monitoring | Track temperatures, flow and leaks | CDU controls (optional BMS integration on the 130 kW air-liquid hybrid model) and DCIM in the project scope |
Cold plates are designed for the chips and servers they fit. Select the cold plate first, then size the rest of the chain around its flow and temperature requirements.
Cold Plates and Manifolds in a Direct-to-Chip System
Lianli's GPU cold plate is rated at 1,000 W with PG25 coolant, a 40 °C inlet, a flow rate of 1 L/min and a flow resistance of 10 kPa. It is made of pure copper and has a G1/4" thread. The GB300 cold plate for the GB300 NVL72 platform is rated at 6,200 W total at a 45 °C inlet and uses UQD04 quick connectors. The AMD SP5 CPU cold plate is rated up to 400 W at 1.5 L/min.
Lianli's 48U liquid-cooled cabinet has 20 UQD04 male connectors, two distribution manifolds and a flow rate of 12 m³/h. Each server's cold plate loop connects through a standard quick connector.
CDUs for Direct-to-Chip Liquid Cooling: Rack Scale to 2 MW
Lianli's CDUs support direct-to-chip deployments at different scales:
- In-rack liquid-to-liquid: 4U 65 kW and 6U 130 kW units, with primary-side temperatures of 30/40 °C and secondary-side temperatures of 40/50 °C, N+1 redundant pumps and dual power supplies.
- In-row liquid-to-liquid: 500, 800, 1,000 and 1,500 kW units on the same temperature pair, with 200 µm primary and 100 µm secondary filtration, plus a 2,000 kW unit. The 500 kW unit has N+1 pumps.
- Air-liquid hybrid: 6 to 18 kW rack units suited to retrofit rooms, and a 130 kW in-row unit that requires no external chilled water.
The 600 kW in-row model lists leak detection, dew point monitoring, pressure protection, heat exchanger blockage detection and remote monitoring. Each model's heat exchange capacity applies at the listed temperatures.
Primary-Side Heat Rejection and Warm-Water Design
Lianli designs the entire system for warm-water operation. The CDU secondary loop runs at 40/50 °C, and the GB300 cold plate has a 45 °C inlet temperature. These temperatures suit dry-cooler free cooling.
Lianli's factory also supplies the dry coolers and cooling towers on the primary side. With cold plates, CDUs and primary-side heat rejection equipment from one supplier, a single quote can cover equipment for both loops.
Leak Testing and Quality Control for Direct-to-Chip Hardware
Lianli's factory quality control starts with supplier approval and sample confirmation. During production, it uses self-inspection, peer checks and dedicated in-process quality control (IPQC) inspections. Finished products undergo performance, safety and control logic tests before they are packed and placed in storage.
The factory's test equipment includes a coordinate measuring machine, a high-pressure burst tester, a pressure pulse tester, a helium mass spectrometer leak detector, a leak monitoring test rig, a flow resistance test bench and an infrared thermal imager. Lianli also offers test products such as a 50 kW in-rack liquid-cooled load bank. In March 2026, Lianli delivered NVIDIA H200 and AMD SP5 liquid cold plates in volume to a customer in Taiwan and provided test reports, including cleanliness and airtightness reports.
A 3 MW Direct-to-Chip Liquid Cooling Project
For an unnamed AI data center project in Xinjiang, Lianli supplied the full direct-to-chip liquid cooling system for 128 NVIDIA H200 GPU servers with a total IT load of about 3 MW. The scope included GPU and CPU cold plates, rack distribution manifolds, row-level and room-level CDUs, outdoor dry coolers, piping and a DCIM system. The target delivery timeline was 60 days from design through acceptance.
Both single-supplier and multi-vendor sourcing can work. Check whether equipment interfaces and flow rates match across layers, who is responsible for the interface between the rack and facility loops, and who will commission the complete system.
Summary
Lianli suits data centers that want one factory to supply and match every layer of direct-to-chip cooling. The range includes 1,000 W GPU and GB300 cold plates, UQD04 manifolds, CDUs from 6 kW to 2,000 kW with a 40/50 °C secondary loop, dry coolers and cooling towers, and in-house leak and pressure testing. Select the cold plate for the chip first, then match the CDU and primary-side heat rejection equipment to it.
Send the server model and project scope through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
What does a direct-to-chip liquid cooling solution include?
A complete solution includes cold plates, rack manifolds and quick connectors, a CDU, primary-side heat rejection and monitoring.
Can I buy only cold plates or only a CDU from Lianli?
Yes. Lianli sells cold plates and CDUs separately, with a minimum order of one unit. Its GPU cold plates are rated at 1,000 W, and its CDUs range from 6 kW to 2,000 kW.
What coolant temperature does Lianli's direct-to-chip design use?
Lianli's CDUs run a 40/50 °C secondary loop. Its GPU cold plate is designed for a 40 °C inlet, and its GB300 cold plate is designed for a 45 °C inlet. This warm-water range suits dry-cooler free cooling.
How does Lianli test direct-to-chip hardware?
Lianli uses helium mass spectrometry for leak detection, high-pressure burst and pressure pulse testing, a flow resistance test bench and infrared imaging. Finished products undergo performance, safety and control logic tests.
Does Lianli's direct-to-chip solution work with GB200 and GB300 servers?
Lianli's direct-to-chip products are compatible with NVIDIA GB300, GB200, B300, B200, H200 and H100 platforms. Its GB300 cold plate fits the GB300 NVL72 compute tray at 6,200 W total with a 45 °C inlet. In a Shenzhen GB200 NVL2 room, Lianli used copper microchannel cold plates with a room-level CDU.
What coolant can a Lianli direct-to-chip loop use?
Lianli's 1,000 W GPU cold plate uses PG25, and its GB300 cold plate can use deionized water or PG25. Lianli's in-row CDUs can use deionized water, an aqueous ethylene glycol solution or an aqueous propylene glycol solution. The 500 kW model can use an aqueous ethylene glycol solution at concentrations up to 40%. Fill the loop with the coolant specified for the cold plate.