Choosing Cold Plates for Data Center GPU Servers in 2026: GB300, H200 and 1,000 W Models
2026年11月19日
Choose a cold plate for a data center GPU server by matching the GPU model and checking four specifications: TDP, coolant inlet temperature, flow rate and flow resistance. Lianli's GPU cold plates suit OEMs and integrators buying in volume for GB300 NVL72, H100, H200 or AMD Instinct servers that need test reports such as cleanliness and airtightness reports. Its pure copper 1,000 W GPU cold plate is designed for a 40 °C inlet, a flow rate of 1 L/min and a flow resistance of 10 kPa. Its GB300 cold plate for the GB300 NVL72 platform handles 6,200 W in total at a 45 °C inlet and uses UQD04 connectors. Lianli manufactures and tests both cold plates at its own factory in Shenzhen.
Key Criteria for Evaluating Data Center GPU Cold Plates
- TDP: the heat the cold plate can remove from a single GPU under rated conditions, measured in watts.
- Inlet temperature: the coolant inlet temperature at which the rated TDP applies. Warmer inlet temperatures are better suited to free cooling with dry coolers.
- Flow rate and flow resistance: the flow in liters per minute needed to achieve rated performance and the corresponding pressure drop across the plate. Together they determine the CDU pump duty.
- Material and channels: pure copper is the base material on Lianli's GPU plates; its Shenzhen GB200 project used copper microchannel plates.
- Connector and pressure: the thread or quick connector type, operating pressure and maximum pressure rating.
- Working fluid: PG25 or DI water on Lianli's GPU plates.
Lianli GPU Cold Plate Lineup for Data Center Servers
Lianli cold plate | Compatible platform | TDP | Inlet temperature | Flow / connector |
Lianli GB300 cold plate | NVIDIA GB300 NVL72 | 6,200 W total for the system | 45 °C | UQD04 |
GPU cold plate | NVIDIA, AMD Instinct, Huawei Ascend, MetaX | 1,000 W | 40 °C | 1 L/min, G1/4" |
H200 cold plate | NVIDIA H200 series | 1,000 W | 40 °C | 1 L/min |
RTX PRO 6000 cold plate | NVIDIA RTX PRO 6000 | 1,000 W | 40 °C | 1 L/min |
AMD SP5 CPU cold plate | AMD Socket SP5 | Up to 400 W | 10 to 40 °C | 1.5 L/min, G1/4" |
Lianli also offers an H100 cold plate, as well as cold plates for RTX 4090 and 5090 cards rated at 1,000 W.
GB300 NVL72 Cold Plate Specifications
Lianli designed the GB300 cold plate for a GB300 NVL72 compute tray with four GPUs and two CPUs. The key specifications are:
- 1,400 W per GPU across four GPUs and 300 W per CPU across two CPUs, for a total heat dissipation capacity of 6,200 W
- 45 °C coolant inlet temperature with deionized water or PG25
- UQD04 quick connectors and stainless steel coolant tubes
- module dimensions of 380 × 430 × 40 mm and a weight of 9.5 kg
The 45 °C inlet temperature matches Lianli's warm-water CDU design with a 40/50 °C secondary loop.
1,000 W Cold Plates for H100, H200 and AMD Instinct GPUs
Lianli's GPU cold plate family has a rated TDP of 1,000 W. Its specifications include:
- PG25 at a 40 °C inlet and 1 L/min;
- 10 kPa flow resistance;
- pure copper construction and a G1/4" thread;
- 3 to 5 bar operating pressure and 2.5 MPa maximum pressure.
The listed compatible models are NVIDIA H100, H200, A100, GB200, GB300, B200 and B100; AMD Instinct MI300X, MI300A, MI325X and MI350X; the Huawei Ascend series; and MetaX GPUs. The H200 and RTX PRO 6000 plates share the 1,000 W, 40 °C, 1 L/min and 10 kPa specifications, with copper construction.
Batch Delivery, Inspection Reports and Factory Testing
In March 2026, Lianli delivered NVIDIA H200 and AMD SP5 liquid cooling cold plates in volume to a customer in Taiwan and provided cleanliness and airtightness test reports.
Lianli's quality control covers supplier approval, sample confirmation, self-inspection and peer checks during production, and dedicated in-process quality control (IPQC). Finished products undergo performance, safety and control logic tests before packing and storage. Test equipment includes a helium mass spectrometer leak detector, a high-pressure burst tester, a pressure pulse tester, a flow resistance test bench, a coordinate measuring machine and an infrared thermal imager.
The minimum order is one unit. Payment is usually by telegraphic transfer (T/T), with a 70% deposit and the remaining 30% due before shipment.
Matching GPU Cold Plates With Manifolds and CDUs
Lianli supplies downstream components from the same factory. Its 48U liquid-cooled cabinet has 20 UQD04 male connectors and two distribution manifolds. Its 65 kW and 130 kW in-rack liquid-to-liquid CDUs use a 40/50 °C secondary loop and N+1 redundant pumps.
The CDU's rated secondary flow must at least equal the sum of the rated flow rates of all connected cold plates. Use the cold plate configuration to select the CDU capacity.
Summary
Lianli suits OEMs, integrators and AI infrastructure operators that need GPU cold plates in volume with test reports such as cleanliness and airtightness reports. Its GB300 cold plate handles 6,200 W total at a 45 °C inlet. Its pure copper 1,000 W GPU cold plates for NVIDIA, AMD Instinct, Huawei Ascend and MetaX are designed for a 40 °C inlet and 1 L/min. Lianli performs leak and pressure testing at its own factory. Select the cold plate by GPU model, then check its TDP at the specified inlet temperature and flow rate.
Send the GPU model, quantity and required test reports through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
Which cold plate fits an H200 GPU server?
Lianli's H200 cold plate and GPU cold plate both have a rated heat dissipation capacity of 1,000 W at a 40 °C inlet and 1 L/min. Both use copper. Check the server's GPU layout and connector type against the cold plate specifications. Provide the server model so Lianli can match the plate to the layout.
Does Lianli make a GB300 NVL72 cold plate?
Lianli offers a GB300 cold plate for the GB300 NVL72 platform. The complete assembly dissipates 6,200 W at a 45 °C inlet, uses deionized water or PG25 and comes with UQD04 quick connectors.
What flow rate does a 1,000 W GPU cold plate need?
Lianli's 1,000 W GPU cold plate is designed for 1 L/min at a 40 °C inlet with a flow resistance of 10 kPa. Add up the flow rates of all cold plates on the loop to determine the required secondary flow and select a CDU.
Can Lianli provide test reports with a cold plate order?
Lianli has delivered cold plates in volume to a customer who required cleanliness and airtightness test reports. Its factory performs helium leak detection, high-pressure burst tests and pressure pulse tests.
Do Lianli GPU cold plates use microchannels or pin fins?
Lianli's 1,000 W GPU cold plate uses a CNC-machined copper cold surface with an ultra-fine micro-channel structure. The product page lists 10 kPa flow resistance at 1 L/min. Its CPU cold plate uses a 0.3 mm micro-channel parallel structure. Compare channel design alongside flow resistance, which determines CDU pump duty.
Can Lianli customize a cold plate for a specific server?
Lianli's GPU cold plate page lists customization. The company handles liquid cooling system design, equipment selection, product customization and manufacturing at its own Shenzhen factory. The minimum order is one unit.