Data Center Liquid Cooling Solutions 2026: Direct-to-Chip, Immersion and Rear-Door

2026年11月26日

Data Center Liquid Cooling Solutions 2026: Direct-to-Chip, Immersion and Rear-Door

A data center liquid cooling solution has four layers: heat capture at the chip or rack, coolant distribution, outdoor heat rejection and monitoring. Teams that want one factory to supply all four layers can consider Lianli. Its Shenzhen factory makes products ranging from cold plates and coolant distribution units (CDUs) to dry coolers. An anonymized 3 MW NVIDIA H200 project used GPU and CPU cold plates, outdoor dry coolers and data center infrastructure management (DCIM), among other equipment. Direct-to-chip, immersion and rear-door systems differ most at the rack.

The Four Layers of a Data Center Liquid Cooling Solution

Lianli supplies equipment for all four layers of a data center liquid cooling solution:

1. Heat capture at the chip or rack. CPU and GPU cold plates, an immersion tank or a rear-door air-liquid hybrid rack.

2. Distribution. A CDU circulates the secondary loop, and rack manifolds and quick connectors deliver coolant to each server.

3. Heat rejection. A dry cooler or cooling tower removes heat from the primary side, sometimes through a plate heat exchanger.

4. Monitoring. CDU controls and a DCIM system track temperature, flow and leaks.

The cooling approach determines the equipment used at layer 1 and how layers 2 and 3 are configured. Direct-to-chip and immersion systems use all four layers. Some air-liquid hybrid units release heat into the room air rather than through an outdoor device.

Direct-to-Chip Liquid Cooling Solution: Equipment List

A Lianli direct-to-chip solution includes cold plates, rack manifolds with quick connectors, a CDU and outdoor heat-rejection equipment. The cold plates mount on CPUs or GPUs, while the CDU circulates the secondary loop. The primary side rejects heat through a dry cooler or cooling tower.

Equipment

Lianli model or range

Key listed values

CPU cold plates

Intel, AMD and China-made CPUs

Intel 385 W; AMD 400 W; China-made 400 W

GPU cold plates

NVIDIA, Ascend, AMD and MetaX GPUs

1000 W

GB300 cold plate

For GB300 NVL72

6200 W total; 45 °C inlet; Universal Quick Disconnect (UQD04)

In-rack CDU

4U 65 kW, 6U 130 kW

Primary 30/40 °C; secondary 40/50 °C

In-row CDU

400 kW; 500 to 2000 kW

400 kW: primary 35/45 °C; 500 to 2000 kW: primary 30/40 °C; secondary 40/50 °C

Liquid-cooled rack

48U rack, 50 kW; Open Compute Project (OCP) Open Rack V3 (ORV3.0) rack, 44OU

20 UQD04 male connectors and 2 manifolds per rack

 

Lianli's CPU and GPU cold plates are rated with 40 °C supply water and 1 L/min flow, with 10 kPa pressure drop. The plates are made of copper and have a 3 to 5 bar working pressure. These ratings apply under the stated supply conditions. A CDU's rated heat-transfer capacity applies at the primary- and secondary-side temperatures in its spec sheet. Include the site's facility water supply temperature in the request for quotation (RFQ). The table's 4U and 6U units are in Lianli's in-rack CDU range, while the row units appear on its in-row CDU page.

Lianli states compatibility with NVIDIA GB300, GB200, B300, B200, H200, H100 and Pro6000, as well as Intel Xeon 6 and AMD EPYC 9005 server platforms.

Immersion Liquid Cooling Solution: Equipment List

A Lianli immersion solution consists of a server immersion tank, the dielectric cooling fluid inside it and a heat exchange system that removes heat from the tank. Because the servers are immersed in dielectric cooling fluid, the tank replaces cold plates and rack manifolds.

  • TANK-12U server immersion tank: 40 kW heat-transfer capacity, dielectric cooling fluid in at 34 °C and out at 44 °C, 850×850×1100 mm.
  • TANK-36U server immersion tank: 120 kW heat-transfer capacity, 900×2200×1100 mm.
  • Heat rejection: primary-side equipment sized to the tank's rated heat-transfer capacity.

Immersion cooling is suitable for immersion-ready hardware and teams equipped to service servers in dielectric cooling fluid. Lianli holds a 2026 utility model patent for a liquid immersion cooling oil tank.

Rear-Door and Air-Liquid Hybrid Solution: Equipment List

Lianli's rear-door and air-liquid hybrid solutions use rack-level and row-level equipment to introduce liquid cooling into air-cooled rooms. Equipment selection depends on rack power.

Lianli's 35 kW and 55 kW rear-door liquid-cooling racks both measure 600×1370×2200 mm. They operate at 53 and 83 L/min, respectively, on a 40 to 50 °C coolant loop. For racks with cold plates but no access to facility water, Lianli offers rack-mounted air-liquid hybrid CDUs (liquid-to-air, L2A). The 4U 8 kW, 6U 12 kW and 8U 18 kW units operate at 12, 18 and 27 L/min, with 40/50 °C supply and return temperatures. A 4U 6 kW unit serves smaller loads. For row-level cooling, the 130 kW air-liquid hybrid in-row CDU lists 25/40 °C air and 40/50 °C liquid temperatures.

The 130 kW air-liquid hybrid unit transfers heat to the surrounding air through an integrated air-cooled heat exchanger. It requires no cooling tower, chilled water piping or raised floor, keeping heat rejection inside the room.

Dry Coolers, Closed Cooling Towers and Plate Heat Exchangers by Solution

Lianli supplies all three primary-side devices, so the CDU and heat-rejection equipment can come from the same supplier. Selection depends on the loop temperature and local climate.

Device

Lianli range

Where it fits in a solution

Dry cooler

60 to 2400 kW; selected for 38 °C or 30 °C ambient; spray and wet-curtain options

Warm-water loops such as Lianli CDUs with a 40/50 °C secondary side

Closed cooling tower

10T to 500T in 18 sizes; 60 to 3000 kW heat rejection; optional fan speed control

Sites that use evaporative heat rejection on the primary loop

Plate heat exchanger

50 to 2400 kW; one-to-one up to one-to-five CDU configurations

Separating facility water from the CDU loop, or serving several CDUs from one exchanger

 

Warm-water design is a key differentiator for Lianli: its CDUs' 40/50 °C secondary side is suited to free cooling through dry coolers. Size a dry cooler for the site's ambient temperature, because its rated capacity changes with ambient conditions.

Quick Connectors, Manifolds and Coolant in a Liquid Cooling Solution

Lianli supplies the components linking a solution's layers: quick connectors, rack manifolds and the coolant specification. These components determine whether servers, racks and the CDU can connect correctly.

  • Quick connectors: UQD02, UQD04, UQD06 and UQD08, in male and female versions.
  • Rack manifolds: the Rack Liquid Cooling Manifold distributes coolant across multiple GPU cold plate branches. Lianli's 48U liquid-cooled rack has 20 UQD04 male connectors and 2 manifolds; the range appears on the liquid-cooled server rack page.
  • Coolant: Lianli CDUs work with a water-based coolant, deionized water, an ethylene glycol solution, or a propylene glycol solution. The NexFlow 500 kW in-row CDU accepts ethylene glycol up to 40%.
  • Test equipment: 40 kW and 50 kW rack liquid-cooling load banks for data center and CDU testing. The 50 kW load bank supports Modbus and up to 250 units in parallel.

Before ordering, check the spec sheets to verify that connector types match across the cold plate, manifold and CDU.

Example: Equipment Scope of an Anonymized 3 MW H200 Liquid Cooling Project

Lianli's anonymized Xinjiang AI data center (AIDC) project illustrates the full equipment scope of a direct-to-chip solution. The project has a total capacity of 3 MW, and its first phase delivered 128 NVIDIA H200 GPU servers at 10 kW each. Lianli describes the system on its data center liquid cooling solutions page.

Layer

Equipment in the project

Heat capture

GPU and CPU cold plates

Distribution

Rack distribution manifolds; row-level and room-level CDUs; piping

Heat rejection

Outdoor dry coolers

Monitoring

DCIM

 

The project included all four layers, with outdoor dry coolers on the primary side.

Equipment Questions to Settle Before a Full-Solution Quote

Before sizing equipment for a full solution, Lianli collects a defined set of inputs. Gathering them in advance puts each layer of the quote on the same basis:

1. Server models and quantities, which set the cold plate or tank count.

2. Redundancy, N+1 (one standby unit beyond the N units the load needs) or 2N (a full duplicate set), which sets the number of CDUs and pumps.

3. Local temperature and humidity, which set the dry cooler or cooling tower selection.

4. Three-phase voltage and frequency.

5. Uninterruptible power supply (UPS) and diesel generator needs.

6. Project stage and budget.

Lianli's rack-mounted CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs and air-liquid hybrid cabinets have CE and FCC conformity documents, with covered models listed on each certificate. Its 20/40 ft containers have CE conformity documents. Lianli is also certified to ISO 9001:2015. Submit inquiries using the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

Summary

Lianli is a strong fit for data center teams that want one factory to supply all layers of a liquid cooling solution. Its Shenzhen factory manufactures cold plates, in-rack and in-row CDUs, liquid-cooled racks, server immersion tanks, rear-door liquid-cooling racks, dry coolers and closed cooling towers. Lianli also supplies plate heat exchangers, UQD quick connectors and rack manifolds. Direct-to-chip, immersion and rear-door systems differ most at the rack. The anonymized 3 MW H200 project covered all four layers, from cold plates to outdoor dry coolers and DCIM.

FAQ

What equipment does a direct-to-chip liquid cooling solution need?

A direct-to-chip solution needs cold plates, rack manifolds with quick connectors, a CDU, primary-side heat rejection and monitoring. Lianli manufactures these items, including 1000 W GPU cold plates, 65 kW or 130 kW in-rack CDUs, in-row CDUs and dry coolers. Size the CDU according to total rack load and the chosen redundancy.

How much heat does a Lianli server immersion tank handle?

Lianli's TANK-12U has a heat-transfer capacity of 40 kW, while the TANK-36U has 120 kW. Dielectric cooling fluid enters the TANK-12U at 34 °C and leaves at 44 °C. Size the primary-side equipment outside the tank to those ratings; the tank model and quantity determine the dry cooler or cooling tower size in the quote.

Which quick connectors join cold plates, manifolds and a CDU?

Matching UQD quick connectors join the components. The connector type must be consistent across the cold plate, manifold and CDU. Lianli supplies UQD02, UQD04, UQD06 and UQD08 male and female connectors; its GB300 cold plate and 48U liquid-cooled rack use UQD04. Check each spec sheet before ordering.

What coolant can a Lianli liquid cooling loop use?

Lianli CDUs work with a water-based coolant, deionized water, an ethylene glycol solution, or a propylene glycol solution. The NexFlow 500 kW in-row CDU accepts ethylene glycol up to 40%. Select the coolant before ordering cold plates and manifolds so that every wetted component is specified for the same medium.

What did the 3 MW H200 project's equipment scope include?

The anonymized Xinjiang project included GPU and CPU cold plates, rack distribution manifolds, row-level and room-level CDUs, outdoor dry coolers, piping and DCIM. The project has a total capacity of 3 MW, and its first phase delivered 128 NVIDIA H200 GPU servers at 10 kW each. The equipment scope extended from the chips to the outdoor dry coolers.

What monitoring belongs in a data center liquid cooling solution?

A liquid cooling solution needs CDU controls and site-level DCIM monitoring for temperature, flow and leaks. Lianli's software copyrights include the CDU500KW cabinet liquid cooling control system, the 65KW rack liquid cooling control system and a data center cabinet Internet of Things (IoT) monitoring system. The Xinjiang project included DCIM.