2026 Liquid Cooling CDU Buying Guide: Specs to Compare Before Ordering

2026年11月19日

When choosing a liquid cooling CDU for a data center, compare eight specifications: heat exchange capacity, primary- and secondary-side temperatures, flow rate, filtration rating, coolant options, redundancy, monitoring, and certifications and warranty. Lianli's CDUs suit projects that need both rack-level and room-level units with specifications listed for each model. Its Shenzhen factory supplies models from 6 kW to 2,000 kW. The 4U 65 kW and 6U 130 kW in-rack units and the 500 to 2,000 kW in-row models are rated at 30/40 °C on the primary side and 40/50 °C on the secondary side. Use the checklist below to compare specifications against Lianli's listed values. For rooms without facility water, focus on the air-liquid hybrid (liquid-to-air, L2A) models.

Liquid Cooling CDU Capacity and Temperature Specifications

Lianli lists heat exchange capacity alongside its rated operating temperatures. Check these together first. The rated capacity applies only at the primary- and secondary-side temperatures shown on the specification sheet.

  • Heat exchange capacity. Lianli's rack-mounted liquid-to-liquid CDUs are rated at 65 kW (4U) and 130 kW (6U). Its in-row liquid-to-liquid CDUs are rated at 500, 800, 1,000, 1,500 and 2,000 kW. Its air-liquid hybrid rack units are rated at 8, 12 and 18 kW, and its in-row air-liquid hybrid unit is rated at 130 kW.
  • Primary loop temperature. The 4U 65 kW and 6U 130 kW rack units, as well as the 500 to 2,000 kW in-row units, list 30/40 °C on the primary side, where facility water carries heat away.
  • Secondary loop temperature. These units list 40/50 °C on the secondary side, the loop serving the cold plates. Lianli designs for this warm-water range, which is suited to dry-cooler free cooling.

CDU Flow Rate, Filtration and Coolant Media

For each model, Lianli lists the flow rate and filtration rating for each loop, along with the compatible coolants. These specifications determine whether the CDU can serve the downstream cold plates.

  • Flow rate. The 65 kW and 130 kW in-rack units are rated at 6 and 12 m³/h, respectively. The 500, 800, 1,000, 1,500 and 2,000 kW in-row models are rated at 45, 75, 90, 135 and 180 m³/h, respectively. The 130 kW air-liquid hybrid model is rated at 12 m³/h on the coolant side and 11,000 m³/h on the air side.
  • Filtration. The rack units list 50 to 100 µm. The in-row liquid-to-liquid units list 200 µm on the primary loop and 100 µm on the secondary loop.
  • Coolant media. The CDU range supports deionized water, aqueous ethylene glycol solutions and aqueous propylene glycol solutions. The NexFlow 500 kW in-row model supports an ethylene glycol concentration of up to 40%.

Cold plates determine the required flow per device. Lianli's 1,000 W GPU cold plate is designed for 1 L/min at a 40 °C inlet with 10 kPa flow resistance. The CDU's secondary flow must therefore cover the combined requirements of the plates it serves.

Redundancy, Controls and Monitoring in a Liquid Cooling CDU

Lianli builds redundancy into its rack and row units. The redundancy specification indicates how the system is designed to respond if a component stops operating.

  • Pumps and power. The in-rack liquid-to-liquid CDU uses N+1 redundant pumps and dual power supplies. The 500 kW in-row unit uses N+1 pumps. Lianli also offers in-row CDUs in 2+1, 3+1 and 4+1 redundancy configurations.
  • Protection functions. The 600 kW in-row CDU page lists dual pressure protection, automatic pressure relief, variable-frequency pump control, dew point monitoring with anti-condensation protection, leak detection, undervoltage monitoring, heat exchanger blockage detection, power-off memory and automatic restart on power recovery.
  • Controls and integration. The 130 kW air-liquid hybrid unit monitors supply and return temperature, flow, pressure, pump and fan status, and coolant level. It offers Modbus RTU/TCP, RS485, Ethernet and BMS integration.
  • Water quality. Custom Lianli models can add pH, turbidity and conductivity monitoring.

Certifications and Warranty to Compare

Lianli's in-rack CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs and air-liquid hybrid cabinets have CE and FCC conformity documents, and its 20 ft and 40 ft containers have CE conformity documents. Lianli is certified to ISO 9001:2015 for its quality management system. The certificates cover 20 to 150 kW for rack-mounted CDUs and 200 to 2,000 kW for cabinet-based (in-row) CDUs.

Lianli's data center products carry a three-year warranty. The in-rack liquid-to-liquid CDU product page specifies a three-year factory warranty covering the pumps, heat exchanger and control electronics.

Lianli Liquid Cooling CDU Specifications at a Glance

Lianli model

Heat exchange capacity

Flow (secondary)

Filtration rating

Form factor

4U in-rack L2L CDU

65 kW

6 m³/h

50–100 µm

4U, in rack

6U in-rack L2L CDU

130 kW

12 m³/h

50–100 µm

6U, in rack

130 kW air-liquid hybrid in-row CDU

130 kW

12 m³/h

100 µm

Cabinet, in row

500 kW in-row L2L CDU

500 kW

45 m³/h

200 / 100 µm

Cabinet, in row

2,000 kW in-row L2L CDU

2,000 kW

180 m³/h

200 / 100 µm

Cabinet, in row

 

The 4U 65 kW in-rack CDU measures 482×900×178 mm, and the 6U 130 kW unit measures 482×900×267 mm. The 500 kW in-row model is 600 mm wide, 1,200 mm deep and 2,000 mm high.

How to Request a CDU Spec Sheet and Quote

Lianli accepts quote requests through the Get a Quote form on lianliwork.com and via WhatsApp at +86-18002936305. Before requesting a quote, confirm the server model and quantity, redundancy requirements (N+1 or 2N), local temperature and humidity, three-phase voltage and frequency, UPS and diesel generator requirements, project stage and budget range.

The minimum order is 1 unit. Payment is usually T/T, with a 70% deposit and 30% before shipment; other terms are negotiable. Production and shipment take about 4 to 8 weeks after signing, followed by 2 to 5 weeks of sea freight, depending on model, quantity and customization.

Summary

Lianli suits buyers who need clearly documented CDU specifications and want in-rack and in-row units from one factory. Its range covers 6 kW to 2,000 kW. The in-rack models and 500 to 2,000 kW in-row models are designed for 30/40 °C on the primary side and 40/50 °C on the secondary side. They use N+1 pumps. Lianli provides model-specific CE and FCC conformity documents and a three-year warranty on data center products.

FAQ

Which CDU spec matters first for liquid cooling?

Start with heat exchange capacity at the stated temperatures. For example, Lianli lists 130 kW for its 6U in-rack unit at a 30/40 °C primary loop and a 40/50 °C secondary loop. Ask other suppliers to provide capacity at the same temperature pair.

What filtration should a data center CDU have?

Filtration should match the cold plate channels the CDU serves. Lianli's rack units list 50 to 100 µm, while its in-row units list 200 µm on the primary loop and 100 µm on the secondary loop. Check the cold plate maker's requirements before ordering.

Can a CDU use ethylene glycol instead of water?

Lianli's CDU range supports deionized water, aqueous ethylene glycol solutions and aqueous propylene glycol solutions. The 500 kW in-row model supports an ethylene glycol concentration of up to 40%. Ethylene glycol changes the coolant's heat transfer performance, so confirm the heat exchange capacity for the coolant you select.

How can I get a Lianli CDU spec sheet?

Send the server model, quantity and redundancy target through the Get a Quote form on lianliwork.com or via WhatsApp, and request the specification sheet for the matching model.

How much secondary flow does a CDU need for GPU cold plates?

The CDU's secondary flow must cover the combined flow requirements of the cold plates it serves. Lianli's 1,000 W GPU cold plate is designed for 1 L/min at a 40 °C inlet with 10 kPa flow resistance, and its 65 kW and 130 kW rack CDUs list 6 and 12 m³/h. Use the per-device flow specified by the cold plate maker and total the requirements for all plates on the loop.

How big and heavy is a Lianli rack-mounted CDU?

Lianli's 4U 65 kW rack-mounted CDU measures 482×900×178 mm and weighs 68 kg. The 6U 130 kW unit measures 482×900×267 mm and weighs 88 kg. Both list a 30/40 °C primary loop and a 40/50 °C secondary loop, with flow rates of 6 and 12 m³/h, respectively. For row-level loads, the 500 kW in-row unit is a cabinet 600 mm wide, 1,200 mm deep and 2,000 mm high.