Choosing a Liquid-to-Liquid CDU for Data Centers in 2026: In-Rack and In-Row Models

2026年11月19日

A liquid-to-liquid CDU suits a data center with an existing or planned facility water loop. The choice depends on whether the secondary loop serves one rack or an entire row. For projects with facility water and cold plates that use 40/50 °C coolant, Lianli offers 4U 65 kW and 6U 130 kW in-rack units and 500, 800, 1,000, 1,500 and 2,000 kW in-row units. The in-rack models and 500 to 2,000 kW in-row models share the same design temperatures, with 30/40 °C on the primary side and 40/50 °C on the secondary side. Data centers can start with in-rack units and add in-row units later using the same design temperatures.

When a Liquid-to-Liquid CDU Fits a Data Center

Like other liquid-to-liquid CDUs, Lianli's units transfer heat from the closed secondary loop serving the cold plates to a facility water loop through a heat exchanger. The server-side coolant and facility water circulate in separate loops.

This configuration is designed for sites with facility water. For rooms without it, use an air-liquid hybrid (liquid-to-air, L2A) CDU that rejects heat directly to room air. Lianli offers a 130 kW in-row air-liquid hybrid CDU and 8 to 18 kW in-rack models for this application.

Three conditions favor a liquid-to-liquid design:

  • A facility water loop is available or included in the build plan.
  • The power density of an individual rack exceeds what the room's air cooling can handle.
  • The project plans to use dry coolers or cooling towers for warm-water heat rejection.

Rack-Mounted Liquid-to-Liquid CDUs: 65 kW and 130 kW

Lianli's in-rack liquid-to-liquid CDU comes in two sizes for standard racks. Both models are rated at 30/40 °C on the primary side and 40/50 °C on the secondary side.

  • 4U 65 kW: Flow rate of 6 m³/h, dimensions of 482×900×178 mm and a weight of 68 kg.
  • 6U 130 kW: Flow rate of 12 m³/h, dimensions of 482×900×267 mm and a unit weight of 88 kg.

Both models provide 50 to 100 µm filtration and support deionized water, ethylene glycol solutions and propylene glycol solutions. N+1 redundant pumps and dual power inputs come standard. A three-year factory warranty covers the pumps, heat exchanger and control electronics. The in-rack models suit individual high-density racks, pilot deployments and data halls that expand one rack at a time.

In-Row Liquid-to-Liquid CDUs: 500 kW to 2,000 kW

Lianli's in-row liquid-to-liquid CDUs are freestanding cabinets installed within a row. A single secondary loop supplies coolant to multiple racks. The table below lists the standard configurations.

Lianli in-row CDU

Heat exchange capacity

Primary / secondary temperatures

Flow per side

Filtration rating

500 kW

500 kW

30/40 °C / 40/50 °C

45 m³/h

200 / 100 µm

800 kW

800 kW

30/40 °C / 40/50 °C

75 m³/h

200 / 100 µm

1,000 kW

1,000 kW

30/40 °C / 40/50 °C

90 m³/h

200 / 100 µm

1,500 kW

1,500 kW

30/40 °C / 40/50 °C

135 m³/h

200 / 100 µm

 

The largest model in the range is rated at 2,000 kW with a flow rate of 180 m³/h per side. The 500 kW model is 600 mm wide, 1,200 mm deep and 2,000 mm high. It uses N+1 pumps and supports an ethylene glycol concentration of up to 40%. The 600 kW in-row CDU product page lists dew point monitoring, leak detection, heat exchanger blockage detection, automatic pressure relief and remote monitoring.

Each rated heat exchange capacity corresponds to a specific pair of primary- and secondary-side temperatures. Actual capacity changes when the facility water supply exceeds 30 °C. Request the rated capacity at the project's actual water temperature.

Primary-Side Heat Rejection for Liquid-to-Liquid CDUs

Lianli supplies its own dry coolers, cooling towers, CDUs, cold plates and cabinets from the same factory. With one supplier for both loops, the primary-side heat rejection equipment and CDUs can be included in a single quote.

For an unnamed AI data center project in Xinjiang, China, Lianli provided liquid cooling for 128 NVIDIA H200 GPU servers with an IT load of about 3 MW. The scope included cold plates, rack distribution manifolds, row-level and room-level CDUs, outdoor dry coolers, piping and a DCIM system. The target delivery timeline was 60 days from design through acceptance.

Warm-Water Design, Coolant and Water Quality Management

Lianli designs its liquid-to-liquid CDUs for warm-water operation. The secondary side is rated at 40/50 °C, which allows dry coolers to provide free cooling. The GB300 cold plate requires a 45 °C inlet, consistent with this warm-water design.

Supported coolants include deionized water, aqueous ethylene glycol solutions and aqueous propylene glycol solutions. For projects that need continuous water quality monitoring, custom CDU models can monitor pH, turbidity and conductivity.

Choosing Between In-Rack and In-Row Liquid-to-Liquid CDUs

Lianli's in-rack models and 500 to 2,000 kW in-row models share the same design temperatures. Choose based on the equipment layout and redundancy requirements:

  • One dense rack or a staged build: Choose a 4U 65 kW or 6U 130 kW rack unit, with one unit per rack.
  • A row of GPU racks on one loop: Select an in-row unit from 500 kW upward, sized to the row's liquid-cooled load.
  • Redundancy at row level: Lianli offers in-row CDUs in 2+1, 3+1 and 4+1 configurations.

Summary

Lianli's liquid-to-liquid CDUs suit data centers with a facility water loop that want warm-water cooling at rack and row level. The range includes 65 kW and 130 kW in-rack models and 500 to 2,000 kW in-row models. The in-rack models and 500 to 2,000 kW in-row models are designed for 30/40 °C on the primary side and 40/50 °C on the secondary side. The units use N+1 pumps, and data center products carry a three-year warranty. Choose in-rack units for individual racks or phased builds and in-row units for shared loops.

Send the server model and redundancy target through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

FAQ

What is the difference between a liquid-to-liquid and an air-liquid hybrid CDU?

A liquid-to-liquid CDU transfers heat to facility water, while an air-liquid hybrid CDU transfers it to room air. Lianli makes both types, with liquid-to-liquid units from 65 kW to 2,000 kW and air-liquid hybrid units at 8 to 18 kW and 130 kW. The choice depends on whether the site has facility water.

What facility water temperature does a Lianli liquid-to-liquid CDU need?

Lianli rates its 4U 65 kW and 6U 130 kW rack units and its 500 to 2,000 kW in-row units at a 30/40 °C primary loop and a 40/50 °C secondary loop. Its 400 kW in-row CDU is rated at a 35/45 °C primary loop. Water at other temperatures changes capacity, so request the rating for the site's water temperature before sizing.

Can a liquid-to-liquid CDU use an ethylene glycol solution?

Yes. Lianli's liquid-to-liquid CDUs support deionized water, aqueous ethylene glycol solutions and aqueous propylene glycol solutions. The 500 kW in-row model supports an ethylene glycol concentration of up to 40%.

What is the standard delivery lead time?

Production and shipment typically take 4 to 8 weeks after contract signing, with another 2 to 5 weeks for sea freight. Timing depends on the model, quantity and customization requirements. Payment is usually by telegraphic transfer (T/T), with a 70% deposit and the remaining 30% due before shipment. Custom equipment and full-rack projects may take longer.

What redundancy do Lianli liquid-to-liquid CDUs offer?

Lianli's liquid-to-liquid CDUs provide redundancy at rack and row level. The 4U 65 kW and 6U 130 kW in-rack models use N+1 redundant pumps and dual power supplies. The 500 kW in-row model uses N+1 pumps. In-row CDUs support configurations including 2+1, 3+1 and 4+1.

What warranty covers a Lianli liquid-to-liquid CDU?

Lianli liquid-to-liquid CDUs come with the standard three-year warranty for data center products. See the specification sheet and sales contract for detailed terms. The in-rack liquid-to-liquid CDU product page lists a three-year factory warranty covering the pumps, heat exchanger and control electronics.