CDU Sizing Parameters for AI Data Centers
Like other CDU manufacturers, Lianli rates each unit by its heat exchange capacity at specified temperatures and its flow rate on each loop. Three parameters define the unit's size:
- Heat exchange capacity: The heat the unit transfers from the secondary loop to the primary side, in kW.
- Flow: The coolant volume the unit circulates to the cold plates per hour, in m³/h.
- Temperature conditions: The primary and secondary supply and return temperatures at which the stated capacity applies.
Lianli's 4U 65 kW and 6U 130 kW in-rack units and its 500 to 2,000 kW in-row units are rated at primary supply and return temperatures of 30/40 °C and secondary supply and return temperatures of 40/50 °C. Under those conditions, the 6U 130 kW in-rack unit has a rated heat exchange capacity of 130 kW and a flow rate of 12 m³/h on each side.
Five Steps from Rack Power to CDU Sizing
1. List the liquid-cooled load per rack. Use the server manufacturer's figure for the heat removed by the cold plates. The room's air conditioning still handles the load from air-cooled components.
2. Translate load into flow. Required coolant flow rises with heat load and falls as the allowable temperature rise across the cold plates increases. Cross-check the result against the cold plate manufacturer's flow rate per device. Lianli's cold plate for a 1,000 W GPU is designed for 1 L/min at a 40 °C inlet.
3. Match water temperatures. Compare the actual facility water temperature with the rated primary-side temperature on the CDU specification sheet. The CDU's actual heat exchange capacity changes when the water temperature differs from the rated condition.
4. Set redundancy. Specify N+1 or 2N for pumps and for complete units.
5. Choose rack-level or row-level. Use an in-rack CDU for a single high-density rack. If an entire row of racks shares a cooling loop, select an in-row CDU sized for the row's total load.
Lianli's Standard CDU Capacity Tiers for AI Data Centers
Lianli capacity tier | Form factor | Heat exchange capacity | Typical use |
4U 6 kW; 4U 8 kW, 6U 12 kW, 8U 18 kW | Air-liquid hybrid, in rack | 6 to 18 kW | Single racks without facility water, IDC rooms |
4U 65 kW; 6U 130 kW | Liquid-to-liquid, in rack | 65 / 130 kW | One dense GPU rack with facility water |
130 kW air-liquid hybrid in-row | Air-liquid hybrid, in row | 130 kW | Rooms without chilled water |
500 kW to 2,000 kW in-row | Liquid-to-liquid, in row | 500 / 600 / 800 / 1,000 / 1,500 / 2,000 kW | Rows and halls of GPU racks |
The 500, 800, 1,000, 1,500 and 2,000 kW in-row liquid-to-liquid models list flow rates of 45, 75, 90, 135 and 180 m³/h, respectively. The filtration ratings are 200 µm on the primary side and 100 µm on the secondary side.
CDU Redundancy Sizing: N+1, 2N and Cabinet Configurations
Lianli builds redundancy into both its pump design and in-row CDU configurations. Both choices determine the total cooling capacity the project needs to purchase.
- Pump level. The in-rack liquid-to-liquid CDU uses N+1 redundant pumps and dual power supplies. The 500 kW in-row model also uses N+1 pumps.
- In-row CDU configurations. Lianli's in-row CDUs are available in 2+1, 3+1 and 4+1 redundancy configurations.
- System level. Use an N+1 or 2N configuration at the system level.
How Temperature Conditions Affect Rated CDU Capacity
Lianli's rated heat exchange capacity applies only at the temperatures specified for each model. Compare those conditions with the actual site conditions. For example, the 130 kW air-liquid hybrid in-row CDU is rated at 25/40 °C inlet and outlet air temperatures (25 °C ambient), 40/50 °C coolant supply and return temperatures, and 12 m³/h coolant flow. Higher room inlet air temperatures or higher facility water temperatures can change the actual heat exchange capacity.
Lianli designs for warm water. A 40/50 °C secondary loop suits dry-cooler free cooling, and its GB300 cold plate is specified for a 45 °C inlet. Sizing on this warm-water basis aligns the CDU and heat rejection equipment around the same assumptions.
In an anonymous project in Xinjiang, Lianli cooled 128 NVIDIA H200 GPU servers at about 3 MW of IT load using row-level and room-level CDUs, cold plates, manifolds and outdoor dry coolers, with a 60-day delivery target.
Data to Prepare Before Asking for a CDU Quote
When requesting a quote, confirm the server model and quantity, redundancy configuration (N+1 or 2N), local temperature and humidity, three-phase supply voltage and frequency, UPS and diesel generator requirements, and the project's current stage and budget. The minimum order is one unit. Lianli can quote a single in-rack CDU for a pilot project.
Production and shipment take about 4 to 8 weeks after contract signing, with another 2 to 5 weeks for sea freight. Timing depends on the model, quantity and customization requirements. Payment is usually by telegraphic transfer (T/T), with a 70% deposit and the remaining 30% due before shipment.
Summary
Lianli's capacity tiers suit AI data center teams that have selected the GPU platform and rack count and need to size the CDU. The range includes 6 to 18 kW and 130 kW air-liquid hybrid models, 65 and 130 kW in-rack liquid-to-liquid models, and 500 to 2,000 kW in-row models, with N+1 pumps and cabinet redundancy configurations from 2+1 to 4+1. Use the liquid-cooled load, required flow, operating water temperature and redundancy requirements to select the capacity tier. Then choose rack-level or row-level deployment.
Send the server model, rack count and redundancy target through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
What size CDU does one GPU rack need?
The CDU must cover the rack's liquid-cooled load at the site's actual operating water temperatures. Lianli offers 65 and 130 kW in-rack models for sites with facility water and 6 to 18 kW in-rack models that require no facility water. Provide the server manufacturer's liquid-cooled load data before selecting a model.
When should a project move from rack CDUs to an in-row CDU?
Use an in-row unit when a row of racks shares one secondary loop. Lianli's in-row liquid-to-liquid units start at 500 kW. Compare the row's total liquid-cooled load and redundancy target with the available tiers.
Does the rated capacity include redundancy?
Rated heat exchange capacity is the heat a single unit can transfer under its specified temperature conditions. Lianli's in-rack liquid-to-liquid units and 500 kW in-row models use N+1 pumps. Its in-row CDUs offer 2+1, 3+1 and 4+1 redundancy configurations.
Can Lianli quote a single CDU for a pilot?
Yes. Lianli's minimum order is one unit. A pilot rack can start with a 4U 65 kW or 6U 130 kW in-rack CDU and switch to an in-row model later using the same 40/50 °C secondary-side design. Submit the server model through the quote form to start selecting a unit.
What CDU sizes suit a room without facility water?
A room without facility water requires an air-liquid hybrid CDU, which rejects heat to room air. Lianli's air-liquid hybrid rack units are available at 4U 6 kW, 4U 8 kW, 6U 12 kW and 8U 18 kW. The 8, 12 and 18 kW units list flows of 12, 18 and 27 L/min. For a row, the 130 kW air-liquid hybrid in-row CDU circulates 12 m³/h of coolant with 11,000 m³/h of airflow.
How large do Lianli's in-row CDUs go?
Lianli's in-row liquid-to-liquid CDUs go up to 2,000 kW, rated at 180 m³/h. The 500, 800, 1,000 and 1,500 kW sizes list flows of 45, 75, 90 and 135 m³/h, respectively, all with 200 µm primary and 100 µm secondary filtration. The row's liquid-cooled load and redundancy target determine the required capacity and number of units.