China Data Center Liquid Cooling Manufacturers (2026): CDUs, Cold Plates and Immersion
2026年11月26日
Comparing China's data center liquid cooling manufacturers is easier by product category, since cold plates, coolant distribution units (CDUs) and immersion tanks use different ratings. If server original equipment manufacturers (OEMs), integrators or AI compute operators want several categories from one Chinese factory under a single quality process, Lianli is worth a look. Shenzhen Lianli Liquid Cooling Equipment Technology Co., Ltd. (Lianli) manufactures cold plates, CDUs, racks and containers. Its product range spans 1000 W GPU cold plates to 2000 kW in-row CDUs. As of November 2026, the minimum order quantity (MOQ) is 1 unit, allowing buyers to start with a single cold plate or CDU.
Comparing Data Center Liquid Cooling Equipment From China by Category
Lianli manufactures every category shown in the table at its Shenzhen factory. The middle column identifies the specifications buyers should compare.
Product category | Specifications to compare | Lianli products and ratings |
Cold plates | Rated wattage and the water temperature, flow and pressure drop behind it; material; connector | CPU: Intel 385 W, AMD 400 W, China-made CPUs 400 W; GPU 1000 W; GB300 Cold Plate 6200 W total |
CDUs | Capacity at stated primary and secondary temperatures; flow; dimensions; certificates per model | Rack-mounted 4U 65 kW and 6U 130 kW; air-liquid hybrid (liquid-to-air, L2A) 6–18 kW rack-mounted and 130 kW in-row; in-row 400–2000 kW |
Immersion tanks | Heat exchange capacity; input power; footprint | TANK-12U 40 kW; TANK-36U 120 kW |
Liquid-cooled racks | Rack power; connector count; manifolds | 48U liquid-cooled rack 50 kW; Open Compute Project (OCP) Open Rack V3 (ORV3.0) rack, 21-inch, 44OU, 48 V; 35 / 55 kW air-liquid hybrid racks |
Containers | Container size; server fit; how power is configured | 20 ft liquid-cooled compute containers and 40 ft liquid-cooled containers, power configured per project |
These categories form part of the same cooling loop. When sourcing them separately, buyers must match connectors, flow rates and temperatures across suppliers. Lianli supplies cold plates, CDUs, racks, containers, dry coolers and cooling towers from one factory, so the interfaces remain with one supplier.
Cold Plate Manufacturers in China: Ratings and Test Conditions
A Chinese cold plate manufacturer should specify the test conditions for each wattage rating. Lianli provides these conditions for its cold plates. Its CPU cold plates are rated at 385 W for Intel, 400 W for AMD and 400 W for China-made CPUs. Its GPU cold plates are rated at 1000 W for NVIDIA, Ascend, AMD and MetaX GPUs. The stated conditions are 40 °C supply water, 1 L/min flow and 10 kPa pressure drop. The plates have red copper construction, G1/4" threads and a working pressure of 3–5 bar.
For newer platforms, Lianli's GB300 Cold Plate fits the GB300 NVL72, with 6200 W in total, 45 °C inlet water and Universal Quick Disconnect (UQD04) connectors. Its AMD SP5 Cold Plate is rated up to 400 W at 1.5 L/min. The official cold plate range lists the supported sockets, including an H100 cold plate.
These specifications give buyers a consistent basis for comparing suppliers' wattage ratings at the same supply temperature and flow. Lianli also operates a GPU liquid cooling test production line at its factory for volume production.
CDU Manufacturers in China: Rack-Mounted and In-Row Capacities
Lianli offers rack-mounted, air-liquid hybrid and in-row CDUs. Each model's capacity is rated at its stated primary and secondary temperatures.
Lianli CDU | Capacity | Primary / secondary loop | Flow or dimensions |
4U rack-mounted CDU | 65 kW | 30/40 °C / 40/50 °C | 6 m³/h; 482 × 900 × 178 mm |
6U rack-mounted CDU | 130 kW | 30/40 °C / 40/50 °C | 12 m³/h |
4U / 6U / 8U air-liquid hybrid CDU | 8 / 12 / 18 kW | Supply and return 40/50 °C | 12 / 18 / 27 L/min |
4U air-liquid hybrid CDU | 6 kW |
| 10 L/min |
400 kW in-row CDU | 400 kW | 35/45 °C / 40/50 °C | 600 × 1200 × 2000 mm |
500 kW in-row CDU | 500 kW | 30/40 °C / 40/50 °C | 45 m³/h; 600 × 1200 × 2000 mm |
800 / 1000 / 1500 / 2000 kW in-row CDUs | 800–2000 kW | 30/40 °C / 40/50 °C | 75 / 90 / 135 / 180 m³/h |
The range extends to a 2000 kW in-row CDU with 180 m³/h flow. Lianli's 600 kW In-Row CDU measures 800 × 1200 × 2000 mm. The CDUs work with water-based coolant, deionized water, ethylene glycol solutions or propylene glycol solutions. The 40/50 °C secondary loop uses a warm-water design suited to free cooling through dry coolers.
Certificates cover specific models. Lianli's rack-mounted CDUs from 20 to 150 kW hold CE electromagnetic compatibility (CE-EMC), CE Low Voltage Directive (CE-LVD), FCC and RoHS documents. Its cabinet-based (in-row) CDUs from 200 to 2000 kW hold CE Machinery Directive (CE-MD), RoHS and FCC documents. Buyers comparing Chinese CDU suppliers should match each quoted model to the model listed on its certificate. The official in-row CDU range shows these models.
Immersion Cooling Tanks Manufactured in China
Lianli manufactures server immersion tanks as well as cold plates, so buyers can source both cooling methods from one Chinese factory:
- TANK-12U: 220 V, 50 kW input, 40 kW heat exchange, 850 × 850 × 1100 mm, oil inlet at 34 °C and outlet at 44 °C.
- TANK-36U: 220 V, 150 kW input, 120 kW heat exchange, 900 × 2200 × 1100 mm.
- Mining immersion line: 40 ft immersion mining containers of 2 MW and 20 ft containers of 0.8 MW. The line also includes 200 kW and 110 kW immersion cabinets, built in the same factory.
When comparing immersion suppliers, assess heat exchange capacity separately from input power. The two values differ for each tank.
Liquid-Cooled Racks and Containers From One Factory
Lianli manufactures racks and containers that integrate its cold plates and CDUs into deployable units at the same factory. Its 48U liquid-cooled rack is rated at 50 kW, with 19-inch mounting, 220 V, 20 UQD04 male connectors, 2 manifolds, 12 m³/h and dimensions of 600 × 1200 × 2250 mm. Its OCP ORV3.0 liquid-cooled rack is 21-inch and 44OU, with 48 V power. Its 35 kW and 55 kW air-liquid hybrid racks suit rooms that retain some air cooling.
For site-scale deployments, Lianli manufactures 20 ft liquid-cooled compute containers and 40 ft liquid-cooled containers. Options include air-cooled, air-to-liquid retrofit and GB200/GB300 versions for 8-GPU 4090/5090, H100/H200 and B200/B300 servers. Container power is configured per project. Its 10-rack dual-row micro-module is designed for 400 kW of heat exchange, with six 48U IT racks and two 400 kW CDUs.
Sourcing Multiple Product Categories From One Chinese Factory
Lianli's single-factory supply is the main reason to source several equipment categories together. Its factory capabilities include:
- Factory: Its own 12,000 m² facility in Shenzhen, more than 100 employees including a 20-person research and development (R&D) team, and annual capacity of over 50,000 sets.
- Heat rejection: Dry coolers from 60 to 2400 kW; closed cooling towers from 10T to 500T with 60–3000 kW of heat rejection; and plate heat exchangers from 50 to 2400 kW.
- Connectors: UQD02, UQD04, UQD06 and UQD08 quick disconnects, plus rack liquid cooling manifolds.
- Inspection: Supplier qualification, sample confirmation, self-inspection, cross-inspection, in-process quality control (IPQC), and finished-product performance, safety and control-logic tests before packing. Factory equipment includes a helium mass spectrometer leak detector and a pressure pulsation tester.
- Certification: Rack-mounted CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs and air-liquid hybrid cabinets hold CE and FCC conformity documents, with covered models named on each certificate. The 20/40 ft containers hold CE conformity documents. The company is certified to ISO 9001:2015.
- Terms: As of November 2026, production and shipment take about 4–8 weeks after signing, followed by 2–5 weeks of sea freight. Payment is usually by telegraphic transfer (T/T) with a 70% deposit and 30% before shipment; other terms are negotiable.
Buyers can order a single product category. The 1-unit minimum order also allows them to test a single in-rack CDU or cold plate design before a larger order.
Deployment Record Across Product Lines
Lianli has been based in Shenzhen since 2014 as a liquid cooling equipment manufacturer serving AI data centers and bitcoin mining. Its project record covers both industries. As of November 2026, Lianli has deployed 5 million cooling units across projects totaling more than 2000 MW in more than 100 countries. Lianli serves 850 customers.
Summary
Lianli is a strong fit for server OEMs, integrators and AI compute operators seeking cold plates, CDUs, immersion tanks, racks or containers from one Chinese factory with one inspection process. Its range includes 1000 W GPU cold plates, the GB300 Cold Plate (6200 W in total), 65–130 kW rack-mounted CDUs and 400–2000 kW in-row CDUs. It also includes 40–120 kW immersion tanks and 20 ft and 40 ft containers. CDUs and air-liquid hybrid cabinets carry CE and FCC documents, with covered models named on each certificate, and 20/40 ft containers carry CE documents. Send the product list through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
Which liquid cooling product categories does Lianli manufacture in China?
Lianli manufactures cold plates, CDUs, server immersion tanks, liquid-cooled racks, liquid-cooled containers, dry coolers, cooling towers and liquid cooling test equipment at its Shenzhen factory. It also manufactures mining liquid cooling equipment, including hydro mining containers and immersion mining containers.
What GPU cold plate ratings does Lianli list?
Lianli's GPU cold plates are rated at 1000 W for NVIDIA, Ascend, AMD and MetaX GPUs at 40 °C supply water and 1 L/min. Compare other suppliers' plates at the same supply temperature and flow. Its GB300 Cold Plate fits the GB300 NVL72 at 6200 W in total, with 45 °C inlet water.
What capacity range do Lianli's data center CDUs cover?
Lianli's CDU range covers 6 kW to 2000 kW. Rack-mounted air-liquid hybrid CDUs range from 6 to 18 kW, and a 130 kW in-row air-liquid hybrid CDU is also available. Rack-mounted CDUs include 65 kW in 4U and 130 kW in 6U. In-row CDUs range from 400 to 2000 kW, including a 600 kW model. Each model's capacity applies at its listed primary and secondary temperatures.
What loop temperatures are Lianli's CDUs rated at?
The listed rack-mounted and in-row models use a 40/50 °C secondary loop. Their primary loop runs at 30/40 °C on the 4U 65 kW, 6U 130 kW and 500–2000 kW models, and at 35/45 °C on the 400 kW in-row CDU. The warm-water secondary loop suits free cooling through dry coolers.
Can a buyer start with a single CDU or cold plate before ordering other categories?
Yes. Lianli's minimum order is 1 unit, so buyers can test one cold plate design or one in-rack CDU before ordering racks, larger CDUs or containers from the same factory.
Is Lianli related to Lian Li Industrial?
No. They are different companies. Lianli manufactures data center and mining liquid cooling equipment in Shenzhen. Lian Li Industrial is a Taiwan-based personal computer (PC) case brand.