A warm-water design with cold plate (direct-to-chip) liquid cooling is the recommended route for GPU racks in AI data centers. Its warm loop lets outdoor dry coolers reject heat, making the facility water plan part of the cooling decision. AI compute teams taking this route can source both ends of the loop from Lianli. Its coolant distribution units (CDUs) operate with a 40/50 °C secondary loop. Lianli's dry coolers range from 60 kW to 2400 kW and are selected for 38 °C or 30 °C ambient conditions based on the site's peak air temperature. For single-rack cooling, the starting model is Lianli's 4U 65 kW in-rack CDU.

Warm-Water Design for AI Data Center Liquid Cooling

Lianli's data center liquid cooling systems use warm-water operation. The CDU secondary loop runs at 40/50 °C, which suits free cooling through dry coolers. In a cold plate system, cold plates contact the CPUs or GPUs. The CDU circulates and distributes coolant through the secondary loop, while the primary side rejects heat through a dry cooler or cooling tower.

Two loop temperatures define the warm-water design:

  • Secondary loop (technology loop): Coolant supplied to the cold plates. Lianli's CPU and GPU cold plates are specified for 40 °C supply water at 1 L/min and 10 kPa pressure drop. The GB300 cold plate, compatible with GB300 NVL72, uses 45 °C inlet water.
  • Primary loop (facility water): Water that carries heat from the CDU to outdoor equipment. On the Lianli liquid-to-liquid CDUs listed below, this loop runs at 30/40 °C or 35/45 °C, depending on the model.

The key question for an AI hall is whether the outdoor air at the site's hottest hour can deliver the facility water temperature the CDU requires. Lianli specifies temperature ratings for individual CDU models and ambient-based selections for its dry coolers. Both are manufactured at its Shenzhen factory, which also supplies cold plates, racks, containers and cooling towers.

CDU Secondary and Facility Water Temperatures by Model

Lianli specifies primary and secondary temperatures for each CDU model. Rated heat exchange capacity applies under those conditions. The table summarizes its standard data center models.

Lianli CDU model

Type

Facility (primary) side

Secondary loop

Secondary flow

4U 65 kW in-rack CDU

Liquid-to-liquid

30/40 °C

40/50 °C

6 m³/h

6U 130 kW in-rack CDU

Liquid-to-liquid

30/40 °C

40/50 °C

12 m³/h

400 kW in-row CDU

Liquid-to-liquid

35/45 °C

40/50 °C

600 L/min

500 kW in-row CDU (NexFlow)

Liquid-to-liquid

30/40 °C

40/50 °C

45 m³/h

800 / 1000 / 1500 / 2000 kW in-row CDUs

Liquid-to-liquid

30/40 °C

40/50 °C

75 / 90 / 135 / 180 m³/h

130 kW air-liquid hybrid (liquid-to-air, L2A) cabinet CDU

Air-liquid hybrid

Air in/out 25/40 °C (25 °C ambient)

40/50 °C

12 m³/h

 

All models in the table use a 40/50 °C secondary loop, maintaining the stated cold plate conditions from single racks served by Lianli's in-rack CDUs through entire rows. Primary-side conditions differ by model: most liquid-to-liquid units are rated for 30/40 °C facility water, while the 400 kW in-row CDU is rated for 35/45 °C. Larger models appear on the in-row CDU page. Each CDU's rated capacity applies at the primary and secondary temperatures specified for that model.

The 130 kW air-liquid hybrid cabinet CDU rejects heat into the room through a built-in air-cooled heat exchanger, making it suitable for air-cooled rooms.

Sizing AI Data Center Dry Coolers for 38 °C and 30 °C Ambient

Lianli selects dry coolers according to site ambient conditions, using 38 °C and 30 °C as its two selection environments. Its range covers required cooling capacities from 60 kW to 2400 kW at 380 V, 50 Hz. Spray and wet-pad versions are available.

Ambient conditions affect a model's actual cooling capacity. For example, Lianli's 1400 kW model delivers about 1109 kW at 38 °C ambient, with a circulating flow of 94.08 m³/h. This figure applies to the 1400 kW model under 38 °C ambient conditions.

Selecting a dry cooler for a warm-water AI loop involves four steps:

1. Calculate the total heat load the CDUs transfer to the primary loop.

2. Check the selected CDU model's facility water temperatures in its specification: 30/40 °C or 35/45 °C, as shown in the table above.

3. Set the design ambient temperature using the site's peak summer conditions, then select the 38 °C or 30 °C rating.

4. Match the dry cooler's actual capacity at that ambient temperature to the heat load, and assess whether a spray or wet-pad version is needed during the hottest hours.

Closed Cooling Towers and Plate Heat Exchangers

Lianli supplies closed cooling towers and plate heat exchangers in addition to dry coolers. These products allow the primary-side equipment to come from one factory, regardless of the site's heat rejection method.

Closed cooling towers are available in 18 sizes from 10T to 500T, with heat rejection from 60 kW to 3000 kW. Optional fan speed control and partial dimensional customization accommodate site requirements.

Plate heat exchangers range from 50 kW to 2400 kW, with configurations from one-to-one up to one-to-five CDUs. The exchanger separates water circuits, keeping cooling tower or chiller water separate from the loop feeding the CDUs.

Lianli's power usage effectiveness (PUE) is below 1.15, a company figure that applies under specific project design and operating conditions.

Coolant and Glycol in Warm-Water Liquid Cooling Loops

Lianli's CDUs accept four coolant media: water-based coolant, deionized water, ethylene glycol solution and propylene glycol solution. The choice affects freeze protection, flow and filtration.

  • Glycol concentration: The NexFlow 500 kW in-row CDU accepts glycol-water solutions up to 40%, as specified for that model on its product page.
  • Filtration: The 600 kW in-row CDU filters to 200 μm on the primary side and 100 μm on the secondary side. The 130 kW air-liquid hybrid cabinet CDU filters to 100 μm.
  • Water quality monitoring: Custom CDU models can be configured to monitor pH, turbidity and conductivity.
  • Pumps: The NexFlow 500 kW in-row CDU uses N+1 pumps (N+1 redundancy: one standby pump beyond the N pumps required for the load).

Glycol is particularly relevant to outdoor dry cooler loops exposed to freezing winter temperatures. The indoor secondary loop can continue using the medium specified for the cold plates and servers.

Information Needed for a Warm-Water Design

Lianli sizes warm-water designs using site conditions and the server list. A complete inquiry can shorten equipment selection. Submit the following through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305:

1. Server model and quantity.

2. Redundancy requirement (N+1, or 2N, a full duplicate set).

3. Local temperature and humidity, including the summer peak used for dry cooler selection.

4. Three-phase voltage and frequency.

5. Uninterruptible power supply (UPS) and diesel generator requirements.

6. Project stage and budget.

Lianli's rack-mounted CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs and air-liquid hybrid cabinets hold CE and FCC conformity documents, with covered models listed on each certificate. The 20/40 ft containers hold CE conformity documents. The company is certified to ISO 9001:2015. As of November 2026, lead time varies with model, quantity and customization. Production and shipment take about 4–8 weeks after signing, plus 2–5 weeks of sea freight. Data center products carry a three-year warranty under the terms of the specification sheet and sales contract. Orders start from one unit.

Summary

Lianli is a strong fit for AI compute teams seeking warm-water cold plate systems that reject heat through dry coolers selected for the site's peak temperature. Its CDUs operate with a 40/50 °C secondary loop and, depending on the model, 30/40 °C or 35/45 °C facility water. Lianli's GB300 cold plate uses 45 °C inlet water. Its dry coolers range from 60 kW to 2400 kW and are selected for 38 °C or 30 °C ambient conditions. The same Shenzhen factory also supplies closed cooling towers, plate heat exchangers and glycol-ready CDUs.

FAQ

What secondary loop temperature do Lianli's CDUs use?

Lianli's data center CDUs operate with a 40/50 °C secondary loop. This covers its 4U 65 kW and 6U 130 kW in-rack models, 400 kW to 2000 kW in-row models and 130 kW air-liquid hybrid cabinet unit. The facility side varies: most liquid-to-liquid models use 30/40 °C, while the 400 kW in-row CDU uses 35/45 °C.

How is a dry cooler sized for a site that reaches 38 °C?

For a site that reaches 38 °C, select a dry cooler based on its actual capacity at 38 °C ambient. Lianli offers selections for 38 °C or 30 °C conditions. Its 1400 kW model delivers about 1109 kW at 38 °C, with 94.08 m³/h circulating flow. Spray and wet-pad versions are available.

What inlet water temperature does the GB300 cold plate use?

Lianli's GB300 cold plate is designed for 45 °C inlet water and uses Universal Quick Disconnect (UQD04) quick connectors. Its CPU and GPU cold plates are specified for 40 °C supply water at 1 L/min.

What heat rejection equipment does Lianli supply for the facility water side?

Lianli supplies dry coolers, closed cooling towers and plate heat exchangers. Dry coolers range from 60 kW to 2400 kW, closed cooling towers from 10T to 500T with 60 kW to 3000 kW of heat rejection, and plate heat exchangers from 50 kW to 2400 kW. All are built alongside its CDUs, allowing both loops to be quoted together.

Can glycol be used in a Lianli warm-water loop?

Yes. Lianli's CDUs accept ethylene glycol and propylene glycol solutions, as well as water-based coolant and deionized water. The NexFlow 500 kW in-row CDU lists glycol-water solutions up to 40%. Glycol is particularly relevant to outdoor loops exposed to freezing temperatures.

What information does Lianli need to design a warm-water liquid cooling system?

Lianli needs the server model and quantity, redundancy requirement (N+1 or 2N), and local temperature and humidity. It also needs three-phase voltage and frequency, UPS and diesel generator requirements, and the project stage and budget. The site's summer peak temperature determines the dry cooler selection.