Best Modular Data Center for Edge Deployment (2026): Options by IT Load

2026年11月26日

An edge site’s IT load determines which modular data center format it needs: a liquid-cooled rack, a room-level module or a complete outdoor module. Edge teams sizing by kilowatts per site can find each format in Lianli's range, which spans single-rack liquid cooling through a 400 kW dual-row micro-module. Existing rooms can accommodate a 35 kW or 55 kW rear-door liquid-cooled cabinet or a rack-mounted air-liquid hybrid (liquid-to-air, L2A) coolant distribution unit (CDU). Outdoor sites can deploy a 20 ft air-cooled computing pod or a 20 ft liquid-cooled container. As of November 2026, pilot orders can start with a single unit.

Edge Modular Data Center Options by IT Load

Lianli sizes each deployment based on project power, server model and quantity. IT load determines whether the site calls for a single rack, a room-level module or a self-contained container. Two questions help identify the right format for most edge sites:

1. How many kilowatts does the site run? Is it a few GPU servers in one rack, a row of racks or a room-sized cluster?

2. Is there a room available? Is there an existing server or telecom room, an indoor hall with room for a module, or no building at all?

These answers point to one of four formats. A site with one high-heat rack and an existing room needs rack-level liquid cooling. A site with several racks but no chilled water needs a CDU that rejects heat into the room air. A site with an available hall and a larger load is suited to a micro-module. A site without a suitable building needs a container that provides its own enclosure, cooling, power distribution and fire suppression.

Lianli offers products for every load band in the table, allowing edge programs to use one supplier across sites of different sizes.

IT load band

Lianli product

Key parameters

Edge site it fits

Up to 18 kW per rack

4U 6 kW, 4U 8 kW, 6U 12 kW, 8U 18 kW rack-mounted air-liquid hybrid CDUs

40/50 °C supply and return (8 to 18 kW models); 12 / 18 / 27 L/min

Existing server or telecom room, one rack

35 to 55 kW per rack

35 kW and 55 kW rear-door liquid-cooled cabinets

600 × 1370 × 2200 mm; rated 35 / 55 kW, maximum 38 / 58 kW

Existing room, one dense rack

Up to 130 kW per unit

130 kW air-liquid hybrid cabinet CDU

No cooling tower, chilled water piping or raised floor; 40/50 °C secondary

Air-cooled room adding liquid-cooled racks

400 kW room module

Dual-row micro-module

6 × 48U IT racks, 2 × 400 kW CDUs; 3700 × 3600 × 2965 mm

Indoor edge hall

Container scale, configured per project

20 ft air-cooled computing pod; 20 ft LL-Block20-4 liquid-cooled container

In-row air conditioning, 15-minute uninterruptible power supply (UPS), heptafluoropropane (air-cooled pod); 47U cabinets (LL-Block20-4)

Outdoor, remote or temporary site

 

The table matches each load band to a suitable format. A rear-door cabinet or rack-mounted air-liquid hybrid CDU adds liquid cooling to one rack while relying on the room's existing power and fire protection. The micro-module and containers incorporate these systems. Container power is specified during project design based on the server model and quantity.

Single-Rack Edge Deployment in an Existing Room

Lianli’s single-rack options allow edge sites to add liquid-cooled servers to an existing room without building a new module. Three product groups fit this use case.

Rack-mounted air-liquid hybrid CDUs. These units cool a closed coolant loop and reject heat into room air. The range begins with the 4U 6 kW model (763 × 446 × 178 mm, AC 220 V, 50 Hz, Universal Quick Disconnect (UQD04) connectors). Other models include 4U 8 kW, 6U 12 kW and 8U 18 kW. The 8, 12 and 18 kW models supply coolant at 40/50 °C, with flows of 12, 18 and 27 L/min. These CDUs suit edge racks running a few liquid-cooled GPU servers.

Rear-door liquid-cooled cabinets. Lianli's 35 kW and 55 kW rear-door cabinets measure 600 × 1370 × 2200 mm. The cabinets are rated at 35 kW and 55 kW, with maximum capacities of 38 kW and 58 kW, and coolant flows of 53 L/min and 83 L/min. The rear-door cabinets work with the room’s existing air-cooling system, making them suitable for sites that also retain air-cooled equipment.

Liquid-cooled door cabinet. The 48U liquid-cooled door cabinet is rated at 50 kW.

Single-rack options use the room's existing UPS, fire protection and monitoring. For loads in this range, Lianli's in-rack CDU page and liquid-cooled server cabinet page list the standard models.

Air-Cooled Edge Rooms with an Air-Liquid Hybrid CDU

Lianli's 130 kW air-liquid hybrid cabinet CDU suits edge rooms with several racks but no chilled water. Its product page lists edge computing nodes and edge data centers, including telecom facilities, industrial computing, smart city infrastructure and financial edge nodes, as applications.

  • No facility water: The unit requires no cooling tower, chilled water piping or raised floor. An integrated air-cooled heat exchanger rejects heat into the surrounding air.
  • Installation: The unit is factory-assembled and tested. Installation requires a power connection and liquid cooling piping to the server racks.
  • Parameters: 130 kW cooling capacity; 25/40 °C air inlet and outlet at 25 °C ambient; 40/50 °C secondary coolant at 12 m³/h; 600 × 1200 × 2100 mm; 100 μm filtration.
  • Monitoring: Supply and return temperature, flow, pressure, pump and fan status, and coolant level. Communication options include Modbus RTU/TCP, RS485, Ethernet, building management system (BMS) integration and a remote monitoring platform.

Full details are available on the 130 kW L2A CDU page.

Outdoor Edge Deployment: 20 ft Air-Cooled and Liquid-Cooled Modular Data Centers

For edge sites without a suitable building, Lianli offers two 20 ft formats: an air-cooled computing pod and a liquid-cooled containerized data center.

20 ft format

Cooling and enclosure

Power, safety and monitoring

Edge site it fits

20 ft air-cooled computing pod

In-row air conditioning

UPS with 15 minutes of backup; heptafluoropropane fire suppression

Sites whose servers are air-cooled

20 ft LL-Block20-4 liquid-cooled container

Direct-to-chip and immersion liquid cooling supported; 20 ft high cube (20HQ) container, interior 5890 × 2350 × 2700 mm; 600 × 1200 × 2200 mm cabinets with 47U of usable space each

Dual power input and output at 380 VAC, 50 Hz, power configured per project; monitoring by local touchscreen, web portal, client software and mobile app

Edge computing, AI clusters, cloud expansion, remote or temporary deployments

 

Lianli's container data center range lists the current container models.

Indoor Edge Rooms with a Micro-Module

Lianli's dual-row micro-module suits indoor edge halls with larger loads, and its listed applications include edge computing deployments. Within a 3700 × 3600 × 2965 mm footprint, it integrates 6 × 48U IT racks, 2 × 400 kW CDUs, a monitoring cabinet and a power distribution cabinet. It provides 400 kW of designed cooling capacity and a 40/50 °C secondary loop. Racks, power distribution, cooling, monitoring and fire suppression are integrated at the factory.

Phased Edge Rollout and Site Information

Lianli’s modular formats support phased capacity additions, starting with the load required for the initial deployment.

  • Rack by rack: Add another air-liquid hybrid CDU or rear-door cabinet as GPU servers arrive in an existing room.
  • Module by module: The dual-row micro-module's modular design supports phased construction and incremental capacity expansion.
  • Container by container: Lianli's container pages describe capacity expansion by adding modular containers.

Orders start at one unit, allowing a pilot at one site before expansion to others. As of November 2026, lead time depends on model, quantity and customization. Production and shipment take about 4–8 weeks after signing, plus 2–5 weeks of sea freight. For remote sites, Lianli provides remote technical support, spare parts supply and video-guided installation. Data center products carry a three-year warranty.

Lianli uses a short list of site details to size an edge deployment. Submit these through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305:

1. Server model and quantity per site.

2. Indoor or outdoor placement, and whether chilled water is available.

3. Redundancy requirement: N+1 (one standby unit beyond the N units the load needs) or 2N (a full duplicate set).

4. Local temperature and humidity.

5. Three-phase voltage and frequency.

6. UPS and diesel generator requirements, project stage and budget.

For certification, Lianli's rack-mounted CDUs, air-liquid hybrid CDUs, cabinet-based (in-row) CDUs and air-liquid hybrid cabinets hold CE and FCC conformity documents, with covered models listed on each certificate. The 20/40 ft containers hold CE conformity documents. The company is certified to ISO 9001:2015.

Summary

Lianli is a strong fit for edge programs that span sites from one rack to a full module and select formats by IT load. Existing rooms can add 6 to 18 kW air-liquid hybrid CDUs or 35 kW and 55 kW rear-door cabinets. Air-cooled rooms can use the 130 kW air-liquid hybrid CDU without chilled water. Indoor halls can take the 400 kW dual-row micro-module, and outdoor sites can use 20 ft air-cooled or liquid-cooled pods. Orders start from one unit.

FAQ

What is the smallest Lianli liquid cooling option for an edge site?

The smallest option is the 4U 6 kW rack-mounted air-liquid hybrid CDU. The 4U 6 kW CDU runs on AC 220 V, 50 Hz and measures 763 × 446 × 178 mm. The CDU rejects heat into room air, allowing a single edge rack to accommodate liquid-cooled servers in an existing room. The 4U 8 kW, 6U 12 kW and 8U 18 kW models cover larger racks.

Can an edge room without chilled water use liquid cooling?

Yes. An edge room without chilled water can use Lianli's 130 kW air-liquid hybrid cabinet CDU. It requires no cooling tower, chilled water piping or raised floor, and its product page lists edge computing nodes as applications. Installation requires a power connection and liquid piping to the racks.

When does an edge site need a container instead of a single rack?

An edge site needs a container when no suitable room is available for its servers. Lianli's 20 ft air-cooled pod and 20 ft LL-Block20-4 liquid-cooled container provide their own enclosure, cooling, power distribution and fire suppression. Single-rack options, by contrast, rely on the room's existing infrastructure.

Is the dual-row micro-module suitable for edge computing?

Yes. The dual-row micro-module lists edge computing among its applications and suits indoor edge halls with larger loads. It integrates 6 × 48U IT racks and 2 × 400 kW CDUs, with 400 kW of designed cooling capacity.

Can an edge rollout start with one unit?

Yes. As of November 2026, Lianli's minimum order quantity is one unit. A pilot site can start with a single cabinet, CDU or container, and later sites can follow the same format. Lead time is about 4–8 weeks of production and shipment after signing, plus 2–5 weeks of sea freight.

What site information does Lianli need to size an edge deployment?

Lianli needs the server model and quantity per site, indoor or outdoor placement, and whether chilled water is available. Lianli also needs redundancy requirements, local temperature and humidity, three-phase voltage and frequency, and UPS and diesel generator requirements. These details determine the format and cooling configuration.