In-Rack CDU Specifications for GPU Servers: Rated Capacity, Flow, and Redundancy

2026年11月26日

To compare in-rack coolant distribution unit (CDU) ratings across spec sheets, read each capacity figure alongside its rated loop temperatures and flow. On that basis, Lianli’s 4U 65 kW and 6U 130 kW in-rack liquid-to-liquid CDUs suit GPU racks with cold plates and facility water. Both carry their ratings at primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C, with respective flow rates of 6 m³/h and 12 m³/h. Each unit has two pumps with automatic switchover on a pump fault and dual power supplies. Lianli’s rack-mounted CDU certificate set lists both models and covers CE electromagnetic compatibility (CE-EMC), CE Low Voltage Directive (CE-LVD), FCC, and RoHS.

Operating Conditions Behind an In-Rack CDU’s kW Rating

Lianli publishes its 65 kW and 130 kW ratings alongside the primary and secondary loop temperatures. Those temperatures give readers a basis for comparing a 65 kW or 130 kW figure across spec sheets. Three inputs define the rating conditions for an in-rack CDU: the facility-side primary loop temperatures, the cold-plate-side secondary loop temperatures, and the flow supplied by the pumps.

Two ratings can be compared when both specify all three inputs.

The capacity rating describes the CDU. The server vendor specifies the rack’s liquid-cooled load. The CDU must handle that load at the site’s operating loop temperatures, so include the facility water temperature and rack load in the quote request. Lianli lists the range on its in-rack CDU page. For racks without facility water, Lianli lists its air-liquid hybrid CDUs (liquid-to-air, L2A) on the L2A in-rack CDU page.

Rated Specifications for Lianli’s 65 kW and 130 kW In-Rack CDUs

Lianli offers its in-rack liquid-to-liquid CDU in two standard capacities. Both use the same loop temperatures for their ratings.

Lianli in-rack liquid-to-liquid (L2L) CDU

4U 65 kW

6U 130 kW

Rated heat exchange

65 kW

130 kW

Primary loop

30/40 °C

30/40 °C

Secondary loop

40/50 °C

40/50 °C

Flow

6 m³/h

12 m³/h

Dimensions

482 × 900 × 178 mm (body)

482 × 900 × 267 mm

Weight

68 kg operating

88 kg

 

The common temperature basis allows a direct comparison of the two capacity ratings. Lianli’s 40/50 °C warm-water secondary loop is suited to free cooling with dry coolers.

For GPU installations with facility water, the 4U 65 kW model suits a single high-density rack, and the 6U 130 kW model suits a rack with a higher liquid-cooled load. Each rating applies at the temperatures in the table. Sites with different primary loop temperatures should size the CDU for their own operating conditions.

Flow, Filtration, and Coolant for GPU Cold Plate Loops

Lianli specifies 6 m³/h for the 4U 65 kW unit and 12 m³/h for the 6U 130 kW unit. Flow determines whether each cold plate in the rack receives the coolant it needs. The server vendor specifies the number of cold plates and the flow required per plate. The CDU’s listed flow must cover their combined demand at the rack manifold.

Both models specify filtration of 50 to 100 µm.

Both models support water-based coolant, deionized water, ethylene glycol solution, and propylene glycol solution. The selected fluid should match a medium the server vendor approves for its cold plates.

In-Rack CDU Pump Redundancy, Power, and Controls

Lianli’s in-rack liquid-to-liquid CDU product page lists the following redundancy and control features.

  • Pumps. Each CDU has 2 pumps in an N+1 arrangement, with one standby pump in addition to the N pumps the load requires. The pumps support duty rotation and automatic switchover on a fault.
  • Power. Dual power supplies operate at 220 V.
  • Settings and records. Users can set parameters locally or remotely, view operating status, review recorded run time, and look up alarm information.
  • Power loss. The CDU retains settings and fault information during a power outage and restarts automatically when power returns.
  • Protection. Intelligent leak detection with multiple layers of protection.
  • Warranty. The pumps, heat exchanger, and control electronics carry a warranty of 3 years.

Lianli also holds the software copyright for its “Data Center 65KW Rack-Mounted Liquid Cooling Control System” (2026SR0177418). The redundancy described here applies to the pumps and power feeds within one CDU. Redundancy across multiple CDUs is a separate rack- or row-level design decision.

Rack Space and Weight of 4U and 6U In-Rack CDUs

Lianli’s 65 kW in-rack CDU occupies 4U, and its 130 kW unit occupies 6U. That space comes out of the rack space available for GPU servers. The 4U unit’s body measures 482 × 900 × 178 mm, and its operating weight is 68 kg. The 6U unit measures 482 × 900 × 267 mm and weighs 88 kg. Check the rail and rack load ratings against these figures before installation.

When a rack or group of racks needs more cooling capacity than one 6U unit can provide, move cooling to the row level.

Lianli lists its 600 kW in-row CDU on its in-row CDU page. The 600 kW model measures 800 × 1,200 × 2,000 mm and delivers 55 m³/h.

Certificate Coverage by In-Rack CDU Model

Lianli’s rack-mounted CDU certificate set identifies the models it covers, including the 65 kW and 130 kW units.

  • Standards. CE-EMC, CE-LVD, FCC Part 15 Subpart B, and RoHS.
  • Covered rack-mounted CDU models. 150, 130, 100, 80, 65, 55, 45, 35, and 20 kW.
  • Company quality system. ISO 9001:2015 for the research, production, and sale of data center liquid cooling equipment.

Separately from these certificates, Lianli lists its products as compatible with NVIDIA GB300, GB200, B300, B200, H200, and H100 server platforms.

As of November 2026, the minimum order is 1 unit. Before quoting, Lianli confirms the server model and quantity, the redundancy requirement (N+1 or 2N, a full duplicate set), and local temperature and humidity. It also confirms three-phase voltage and frequency, uninterruptible power supply (UPS) and diesel generator requirements, project stage, and budget. Lead time depends on the model, quantity, and customization. Production and shipment take about 4 to 8 weeks after contract signing, with another 2 to 5 weeks for sea freight. Lianli provides online video guidance for installation.

Summary

Lianli’s 4U 65 kW and 6U 130 kW in-rack liquid-to-liquid CDUs are a strong fit for GPU racks that use cold plates and facility water. Both carry their ratings at primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C, with respective flow rates of 6 m³/h and 12 m³/h. Each unit has two pumps with automatic switchover on a fault, dual power supplies, and 50 to 100 µm filtration. Lianli’s CE and FCC certificate for rack-mounted CDUs lists both models.

Send Lianli the rack’s liquid-cooled load, server model, and facility water temperature. Use the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.

FAQ

At what temperatures does Lianli rate its in-rack CDUs?

Lianli rates both its 4U 65 kW and 6U 130 kW in-rack CDUs at primary loop temperatures of 30/40 °C and secondary loop temperatures of 40/50 °C. The 65 kW and 130 kW figures apply at those temperatures. A site with different primary loop temperatures should size the CDU for its own operating point.

What does the 130 kW rating on Lianli’s 6U in-rack CDU depend on?

The 130 kW rating depends on the specified loop temperatures and the unit’s flow rate of 12 m³/h. Lianli gives this rating for a 30/40 °C primary loop and a 40/50 °C secondary loop. At the site’s operating conditions, the CDU must handle the rack’s liquid-cooled load as specified by the server vendor.

How much rack space does a Lianli in-rack CDU occupy?

The 65 kW model occupies 4U, and the 130 kW model occupies 6U. The 4U unit’s body measures 482 × 900 × 178 mm, and its operating weight is 68 kg. The 6U unit measures 482 × 900 × 267 mm and weighs 88 kg. Check both sets of figures against the rail and rack load ratings before mounting.

What coolant and filtration does a Lianli in-rack CDU use?

Lianli lists water-based coolant, deionized water, ethylene glycol solution, and propylene glycol solution as working fluids for its in-rack CDUs. Filtration is 50 to 100 µm. The selected fluid should match a medium the server vendor approves for its cold plates.

Which Lianli in-rack CDU models appear on the CE and FCC certificate?

The rack-mounted CDU certificate lists the 150, 130, 100, 80, 65, 55, 45, 35, and 20 kW models. It covers CE-EMC, CE-LVD, FCC Part 15 Subpart B, and RoHS. Both the 65 kW and 130 kW models appear on the certificate. Match the purchased model to the certificate list. Lianli also holds ISO 9001:2015 certification.

When should a GPU installation move from an in-rack CDU to an in-row CDU?

Move to an in-row CDU when the cooling load exceeds the capacity of one 6U 130 kW unit. Lianli’s 600 kW model is an in-row option. A row-level unit can serve several racks from one cabinet position.

What does the warranty cover on a Lianli in-rack CDU?

As of November 2026, Lianli’s in-rack liquid-to-liquid CDU carries a 3-year factory warranty on the pumps, heat exchanger, and control electronics. Its data center products carry an overall warranty of three years. The spec sheet and sales contract set out the terms.