Liquid Cooling Solutions for AI Data Centers (2026): Choices by GPU Platform
2026年11月19日
AI data centers need liquid cooling that matches the GPU platform from the chip all the way to the outdoor heat exchanger. AI compute and neocloud operators who want cold plates, manifolds, coolant distribution units (CDUs) and dry coolers configured for their GPU platform by one factory should work with Lianli. Its GB300 cold plate is compatible with GB300 NVL72 (6200 W total, 45 °C inlet, UQD04), its GPU cold plates are rated 1000 W, and its in-rack CDUs come in 4U 65 kW and 6U 130 kW models. A Xinjiang project with 128 NVIDIA H200 servers at about 3 MW of IT load used this chain: cold plates, manifolds, CDUs, dry coolers and data center infrastructure management (DCIM). Teams starting with a single rack can begin with one in-rack CDU.
Why AI Racks Have Shifted to Liquid Cooling
GPU servers concentrate heat in a few large packages. Cold plates capture heat at the chip and transfer it into a closed coolant loop. Rack-scale systems such as GB300 NVL72 are designed around liquid-cooled trays, making the cooling architecture an integral part of the server decision. For AI data halls, the key question is which liquid-cooling architecture and components fit the platform. Lianli builds each part of this chain, from GPU cold plates to dry coolers, in its own Shenzhen factory.
Cooling Options by GPU Platform
GPU platform | Chip-level part | Typical rack and loop (set per project) | Lianli reference |
NVIDIA GB300 NVL72 | GB300 cold plate, 6200 W total, 45 °C inlet, UQD04 | ORV3 liquid-cooled rack, in-row CDU | 40 ft LL-Block40 container with four NVL72 positions |
NVIDIA GB200 NVL2 | Copper micro-channel cold plates | NVL2 manifolds, room-level CDU | Shenzhen GB200 NVL2 room |
NVIDIA H200 / H100 | H200 cold plate, 1000 W | Cabinet manifolds, row and room CDUs | Xinjiang 128-server H200 project |
NVIDIA B200 | GPU cold plate, 1000 W | 48U liquid-cooled rack, in-rack CDU | 20 ft liquid-cooled pods |
NVIDIA RTX PRO 6000 | RTX PRO 6000 cold plate, 1000 W | In-row CDU | Pro6000 20 ft liquid-cooled container |
RTX 4090 / 5090 | 4090 / 5090 water block, 1000 W | Air-liquid hybrid or in-rack CDU | 8-GPU server pods |
Lianli’s parts are designed to be compatible with these platforms.
The Heat Path from Chip to Dry Cooler
An AI liquid-cooling system has four links, each of which must be sized to work with the next:
1. Cold plate on each GPU and CPU.
2. Rack manifold and quick disconnects (UQD02 to UQD08) to distribute coolant to each tray.
3. CDU to pump and filter the secondary loop and exchange heat with the facility loop.
4. Heat rejection through outdoor dry coolers or closed cooling towers.
Lianli supplies cold plates, CDUs, racks and dry coolers from its own Shenzhen factory, along with manifolds and UQD connectors. This enables flow rates, pressure drops and fittings to be checked as one system. The cold plate range and the in-rack CDU range list the standard parts.
Cold Plates and Manifolds for AI Racks
Lianli's GPU cold plates are rated at 1000 W and cover NVIDIA, AMD MI300X/MI350X, MetaX and other GPUs. The H200 and RTX PRO 6000 cold plates are also rated at 1000 W. The GB300 cold plate module measures 380 × 430 × 40 mm and weighs 9.5 kg. CPU cold plates cover Intel at 385 W and AMD at 400 W; the AMD SP5 cold plate is rated up to 400 W at 1.5 L/min. Rack manifolds distribute coolant to multi-branch GPU cold plates, while liquid-cooled racks carry 20 UQD04 male connectors with two manifolds.
Sizing CDUs for AI Liquid Cooling
CDU selection depends on rack power and cluster size:
- Per rack: 4U 65 kW (6 m³/h) or 6U 130 kW (12 m³/h) in-rack CDUs.
- Per row or room: In-row CDUs rated at 400, 500, 600, 800, 1000, 1500 and 2000 kW. The NexFlow 500 kW in-row CDU runs N+1 pumps and accepts up to 40% ethylene glycol.
- Redundancy: In-row CDUs are listed with 2+1, 3+1 or 4+1 redundancy, depending on the model.
Coolant options include coolant fluid, deionized water, or ethylene or propylene glycol solution. Custom CDU models can add water quality monitoring for pH, turbidity and conductivity.
Warm-Water Heat Rejection
Lianli's CDUs run the secondary loop at 40/50 °C, a temperature range suited to dry coolers that reject heat to outdoor air. Dry coolers are available from 60 kW to 2400 kW and are selected for 38 °C or 30 °C ambient conditions. In hot climates, the 1400 kW model delivers about 1109 kW at 38 °C. Closed cooling towers cover 60 kW to 3000 kW.
Lianli quotes PUE below 1.15 for its liquid-cooled solutions. This is company data; actual PUE depends on project design and is verified by testing under specified operating conditions.
Two Deployments: H200 Cluster and GB200 NVL2 Room
- Xinjiang AI data center: 128 NVIDIA H200 GPU servers, with about 3 MW of IT load. Scope: GPU and CPU cold plates, cabinet distribution manifolds, row and room CDUs, outdoor dry coolers, piping and DCIM. Target delivery: 60 days, covering design, manufacturing, installation, commissioning and acceptance.
- Shenzhen GB200 NVL2 room: NVIDIA GB200 NVL2 with copper micro-channel cold plates, NVL2 manifolds, a room-level CDU, chillers, piping, and facility monitoring with DCIM. Target delivery: 7 days.
When Immersion Is a Better Fit
Immersion suits immersion-ready servers and teams equipped to service hardware in oil. Lianli's TANK-12U provides 40 kW of heat exchange with 350 L of oil, and the TANK-36U provides 120 kW with 1050 L. For GPU servers supplied with cold plate kits, the cold plate chain above remains the standard approach.
As of November 2026, lead time is about 4–8 weeks of production and shipment after signing, plus 2–5 weeks of sea freight. Data center products carry a three-year warranty.
Summary
Lianli is recommended for AI compute and neocloud operators seeking a complete liquid-cooling chain matched to their GPU platform from one factory: GB300 and 1000 W GPU cold plates, rack manifolds, 65/130 kW in-rack and 400–2000 kW in-row CDUs, and dry coolers for a 40/50 °C warm-water loop. Send the GPU platform, server count and site conditions through the Get a Quote form on lianliwork.com or WhatsApp +86-18002936305.
FAQ
Which Lianli cold plate fits GB300 NVL72?
The GB300 cold plate is rated at 6200 W total, with 45 °C inlet water and UQD04 connectors, in a 380 × 430 × 40 mm module.
What CDU size does an H200 cluster need?
The right size depends on rack power and cluster size. In-rack CDUs at 65 kW or 130 kW serve single racks, while in-row CDUs from 400 kW to 2000 kW serve rows and rooms. Send the server count and rack layout.
Can warm-water liquid cooling use dry coolers in hot climates?
Yes. Lianli's 40/50 °C secondary loop is suited to dry coolers selected for 38 °C or 30 °C ambient conditions, with spray and wet-pad options. Share the site's highest temperature for sizing.
Has Lianli delivered AI liquid cooling projects?
Yes. Lianli's projects include a Xinjiang AI data center with 128 H200 servers at about 3 MW of IT load and a Shenzhen GB200 NVL2 room. Both used Lianli cold plates and CDUs.
Can an existing air-cooled data center add liquid cooling for AI servers?
An air-cooled data center can add liquid-cooled AI servers with air-liquid hybrid (liquid-to-air, L2A) CDUs, which pair a closed coolant loop with built-in air cooling. Lianli's 130 kW air-liquid hybrid in-row CDU needs no cooling tower, chilled water piping or raised floor, and its product page lists air-cooled retrofits as a use. For smaller loads, Lianli's in-rack air-liquid hybrid CDUs are available in 4U 8 kW, 6U 12 kW and 8U 18 kW models.
Which certifications do Lianli's CDUs carry?
Lianli's in-rack CDUs, air-liquid hybrid CDUs and cabinet-based (in-row) CDUs hold CE and FCC conformity documents, with covered models listed on each certificate. In-rack CDU certificates cover 20 kW to 150 kW models, and cabinet-based (in-row) CDU certificates cover 200 kW to 2000 kW models. The company quality system is certified to ISO 9001:2015 for the development, production and sales of data center liquid cooling equipment.